Fluke 1748/15/EUS Power Quality Logger with 60 cm 1,500A iFlex
- 60 cm iFlex current clamp for safe measurements up to 1,500A
- EUS version compliant with regional electrical standards
- 16-bit resolution at 10.24 kHz synchronous sampling rate
- Comprehensive power quality analysis including harmonics and flicker
- Multiple circuit type support: 1Φ, split phase, 3Φ delta/wye
- Internal flash memory for long-term data logging
- Li-ion battery with typically 4 hours on-battery runtime
- Secure Purchase
- Fast Delivery
- Genuine Guarantee
- Online Payment
Description
Battery runtime note (Fluke 1748): Published on-battery runtime is typically 4 hours with the Li-ion pack (3.7 V, 9.25 Wh). Runtime depends on measurement load and is not a simple Wh÷VA calculation from the MA-C8 adapter power rating.
The Fluke 1748/15/EUS Power Quality Logger is a sophisticated instrument designed for professionals who need to analyze and troubleshoot power distribution systems. Engineers and technicians rely on this device to capture voltage and current waveforms, measure harmonic distortion, and identify power quality issues that can affect equipment performance and longevity. With its flexible iFlex current probe, the logger can measure high currents up to 1,500 A safely without breaking the circuit, making it ideal for industrial and commercial installations where space and access are limited.
Fluke 1748/15/EUS Key Features
This Power Quality Logger delivers precise electrical measurements with 16-bit resolution and a sampling frequency of 10.24 kHz, synchronized to the mains frequency for accurate data capture. It supports a wide range of circuit configurations including 1-phase, split phase, and various 3-phase arrangements such as delta and wye configurations. The device stores data internally to flash memory, capable of holding typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events. Key features include comprehensive power quality measurements covering voltage harmonics, current harmonics, flicker, and mains signaling, as well as the ability to record events such as dips, swells, and inrush currents.
- Voltage range: 100 V to 500 V using safety plug input
- Power supply: 100 V to 240 V MA-C8 with standard IEC C7 power cord
- Power consumption: Maximum 50 VA (max. 15 VA with MA-C8 adapter)
- Efficiency: ≥ 68.2% in accordance with energy efficiency regulations
- Battery: Li-ion 3.7 V, 9.25 Wh, customer-replaceable
- On-battery runtime: Typically 4 hours
- Charging time: Less than 6 hours
- Resolution: 16-bit synchronous sampling
- Sampling frequency: 10.24 kHz at 50/60 Hz
- Input signal frequency: 50/60 Hz (42.5 to 69 Hz)
- Circuit types: 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, and more
- Data storage: Internal flash memory, typical 20 sessions of 4 weeks
Who Needs the Fluke 1748/15/EUS?
Electrical engineers and maintenance technicians will find the Fluke 1748/15/EUS indispensable for conducting energy audits, commissioning new installations, and diagnosing persistent power quality problems. Facility managers responsible for optimizing energy efficiency and reducing operational costs will appreciate the detailed data logging capabilities that help identify areas for improvement. Contractors and consulting engineers specifying power systems rely on this logger to verify that electrical distribution equipment meets design specifications and regulatory requirements before handover.
The logger’s versatility makes it suitable for a broad spectrum of applications, from simple voltage profiling in residential split-phase systems to complex harmonic analysis in large industrial 3-phase wye and delta networks. Its ability to measure interharmonics and total demand distortion (TDD) provides insights that basic multimeters cannot offer, making it a critical tool for anyone specifying or maintaining electrical infrastructure where power quality directly impacts productivity and equipment life.
Fluke 1748/15/EUS Applications
In industrial settings, the Fluke 1748/15/EUS is used to monitor the performance of variable frequency drives (VFDs), identify harmonic distortion generated by non-linear loads, and ensure compliance with IEEE 519 harmonic limits. Engineers can use the device to troubleshoot nuisance tripping of circuit breakers, locate sources of electromagnetic interference, and verify power factor correction capacitor performance. The logger is also effective for studying load patterns and demand charges, providing data that can support efforts to shift usage to off-peak periods and reduce electricity costs.
Commercial building managers can deploy the Fluke 1748/15/EUS to analyze power quality across multiple floors or tenants, identifying equipment that causes voltage fluctuations or harmonic pollution. Utility companies and energy auditors rely on this instrument for demand-side management studies and to verify the quality of power delivered to commercial and industrial customers. Additionally, the device serves as a valuable research tool for studying power electronics, renewable energy integration, and the impact of modern electronic equipment on the electrical grid.
Why Buy Fluke 1748/15/EUS from MME?
When you choose to buy the Fluke 1748/15/EUS from MME, you are investing in authenticity and reliable after-sales support. In the region, MME ensures that every unit is genuine Fluke equipment backed by the manufacturer’s warranty and calibration certificates. Our team of technical specialists is available to assist with product selection, helping you determine if the EUS version meets your specific regional requirements and answering any technical questions you may have about the logging capabilities or data analysis software.
MME provides a seamless purchasing experience with fast shipping across the UAE and secure payment options. We understand that downtime is costly, which is why we prioritize efficient order processing and delivery. By purchasing from mme-ae, you also gain access to our comprehensive resource library, including user manuals, application notes, and firmware updates, ensuring you get the most out of your power quality logging investment.
Start your power quality analysis today — order the Fluke 1748/15/EUS from MME and ensure your electrical systems operate at peak efficiency. Our friendly team is ready to help you find the right solution for your specific monitoring needs.
Fluke 1748/15/EUS Specifications
| Electrical Specifications | |
| Power Supply | |
| Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit |
| 100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7) | |
| Power consumption | Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter) |
| Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations) |
| Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input |
| Mains power frequency | 50/60 Hz ±15% |
| Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
| On-battery runtime | Typically 4 hours |
| Charging time | < 6 hours |
| Data Acquisition | |
| Resolution | 16-bit synchronous sampling |
| Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency |
| Input signal frequency | 50/60 Hz (42.5 to 69 Hz) |
| Circuit types | 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies) |
| Data storage | Internal flash memory (not user replaceable) |
| Memory size | Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events |
| Basic Interval | |
| Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
| Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
| Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms) |
| Demand Interval (Energy Meter Mode) | |
| Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
| Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off |
| Power Quality Measurements | |
| Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation |
| Averaging interval | 10 min for all parameters 2 hrs (long term Flicker PLT) 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT) |
| Individual harmonics | 2nd to 50th harmonic Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only |
| Interharmonics | 1st to the 50th interharmonic |
| Total harmonic distortion | Calculated on 50 voltage harmonics |
| Events | Voltage: dips, swells, interruptions, current: inrush current 1748: mains signaling, transients (low frequency) |
| Triggered recordings | RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30) |
| Waveform of voltage and current up to 200 ms, 10/12 cycles | |
| Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s | |
| Inrush | RMS profile based on 1/2 cycle RMS steady state triggering |
| Flicker | In accordance with IEC 61000-4-15 and IEEE 1453 |
| Mains signaling | Two user defined frequencies up to 3 kHz |
| PQ Health | Summarizes power quality measurements in one table. Detailed data available for each parameter |
| EN 50160 | Compliance with standard |
| Programmable PQ limits | Enables user defined limits for local standards compliance |
| Standards Compliance | |
| Harmonics | IEC 61000-4-7: Class 1 |
| IEEE 519 (short time and very short time harmonics) | |
| Power quality | IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device) |
| Power | IEEE 1459 |
| Power quality compliance | EN 50160 |
| Safety | General: IEC 61010-1: Pollution Degree 2 |
| Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V | |
| Power Supply: Overvoltage Category IV, Pollution Degree 2 | |
| Li-ion Battery: IEC 62133 | |
| Interfaces | |
| USB-A | File transfer via USB flash drive, firmware updates, max. supply current: 120 mA |
| Wi-Fi (free with product registration) | File transfer and remote control via direct connection or Wi-Fi infrastructure |
| Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or Wi-Fi/BLE adapter, check for availability) |
| USB-mini | Data download device to PC |
| Voltage Inputs | |
| Number of inputs | 4 (3 phases referenced to neutral) |
| Maximum input voltage | 1000 Vrms, CF 1.7 |
| Input impedance | 10 MΩ |
| Bandwidth | 42.5 Hz to 3.5 kHz |
| Scaling | 1:1 and variable |
| Measurement category | 1000 V CAT III/600 V CAT IV |
| Current Inputs | |
| Number of inputs | 4 (3 phases and neutral), mode selected automatically for attached sensor |
| Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8 |
| Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range | |
| Range | 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24 |
| 3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24 | |
| 6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36 | |
| 40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL | |
| Bandwidth | 42.5 Hz – 3.5 kHz |
| Scaling | 1:1 and variable |
| Auxiliary Inputs | |
| Number of inputs | 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously) |
| Input range | 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s |
| Scale factor | Format: mx + b (gain and offset) user configurable |
| Displayed units | User configurable (7 characters, for example, °C, psi, or m/s) |
| Wireless Bluetooth connection (check for availability) | |
| Number of inputs | 2 |
| Supported modules | Fluke Connect® 3000 series |
| Acquisition | 1 reading/s |
| Environmental Specifications | |
| Operating temperature | -25 °C to +50 °C (-13 °F to 122 °F)1 |
| Storage temperature | Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F) |
| Operating humidity | IEC 60721-3-3: 3K6: |
| -25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 % | |
| 40 °C (104 °F): 55 % | |
| 50 °C (122 °F): 35 % | |
| Operating altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
| Storage altitude | 12,000 m |
| Enclosure | IEC 60529: IP50 |
| IEC 60529: IP65 with IP65 rated voltage connector | |
| Vibration | IEC 60721-3-3 / 3M2 |
| Electromagnetic compatibility (EMC) | EN 61326-1: Industrial CISPR 11: Group 1, Class A |
| IEC 61000-6-5 Power station environment | |
| Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) | |
| USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |
| General Specifications | |
| Warranty | Two-years (battery not included) |
| Accessories: one-year | |
| Calibration cycle: two-years | |
| Dimensions | 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in) |
| Weight | Instrument: 1 kg (2.2 lb) |
| Tamper protection | Accept securing cables (max. Φ 6mm) |
| 1Warm up the product to -10 °C (+14 °F) before you power the unit on | |
| i17XX-FLEX1.5KIP Flexible Current Probe Specifications | |
| Measuring range | 1 to 150 A ac/10 to 1500 A ac |
| Probe cable length | 610 mm (24 in) |
| Probe cable diameter | 7.5 mm (0.3 in) |
| Weight | 170 g (0.38 lb) |
| Minimum bending radius | 38 mm (1.5 in) |
| Nondestructive current | 100 kA (50/60 Hz) |
| Temperature coefficient over operating temperature range |
0.05 % of reading/°C (0.028 % of reading/°F) |
| Working voltage | 1000 V CAT III, 600 V CAT IV |
| Output cable length | 2.0 m (6.5 ft) |
| Probe cable material | TPR |
| Weight | 115 g |
| Probe cable material | TPR |
| Coupling material | POM + ABS/PC |
| Output cable | TPR/PVC |
| Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F) |
| Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F) |
| Relative humidity, operating | 15% to 85% non-condensing |
| IP rating | IEC 60529: IP65 |
| Warranty | One-year |