Megger FREJA 546 Relay Test System
The FREJA 546 Relay Test System is a versatile and advanced tool designed for testing protective relays in power systems. It offers precise and efficient testing capabilities, ensuring the reliability and optimal performance of relay devices used in electrical substations.
- In-stock items are delivered within 2 business days.
- We are not Supporting COD Payments Terms Outside UAE
- For out-of-stock items, delivery may take 2 to 4 business weeks.
Order Via phone number
FREJA 546 Relay Test System
The FREJA 546 relay test system is a versatile and portable instrument designed for secondary testing of protection relays. Operable through a user-friendly touchscreen interface or computer control via FREJA Win software, it offers manual, steady-state, and dynamic testing with a high-resolution TFT LCD display. Equipped with built-in preset test routines and the ability to save test data, it ensures efficient testing of protection relays and schemes. Additionally, the system supports automatic testing through FREJA Remote on a Windows 10 PC. The optional FREJA Win software provides legacy support for various protection tests, making it a comprehensive solution for relay testing needs.
Key Features of the FREJA 546 Relay Test System:
The Megger FREJA 546 Relay Test System represents a cutting-edge solution for the secondary testing of protection relays. This system is renowned for its versatility, portability, and high performance, making it suitable for a wide range of testing applications in the field of electrical engineering and power system maintenance.
- Automated Testing Capability: The FREJA 546 is equipped with FREJA Win software, which allows for fully automated testing. This software is designed to handle various testing routines, enabling users to conduct comprehensive tests with minimal manual intervention.
- Standalone Operation: One of the standout features of the FREJA 546 is its ability to operate independently of a PC. It incorporates an intuitive, high-resolution graphic touchscreen, ensuring ease of use and efficiency in field operations. This allows technicians to perform tests directly on the device without the need for external computer equipment.
- Robust Output Specifications: The system provides four voltage channels and three current channels. Additionally, it offers convertible voltage channels that can be adapted to provide one voltage and six current outputs, delivering up to 60 Amps and 300 VARMS per phase. This high current and high power output make it exceptionally capable for demanding test environments.
- Advanced Synchronization and Testing Features: It includes dynamic GPS satellite synchronized end-to-end testing capabilities, ensuring precise coordination in complex testing scenarios involving multiple locations. The FREJA 546 also supports IEC 61850 testing, which is crucial for integrating and automating substation communications and control.
- User-Friendly Interface: The device features a large, full-color TFT LCD touchscreen display that offers high resolution and clarity for easy viewing of test procedures and results. FREJA Local, the built-in software, provides an array of preset test routines for automatic testing of protection relays and schemes. Its user interface simplifies the selection of test functions through menu screens and touchscreen function buttons.
- Data Management and Transfer: Test results and setups can be saved directly on the FREJA Local memory and can be transferred via USB drive. This feature is essential for maintaining records of tests and printing detailed test reports. The Microsoft Explorer-style display allows users to organize their test data efficiently.
FREJA 546 Specifications
- Automation Options: Fully automated testing with FREJA Win software, enabling efficient and
- comprehensive relay testing.
- Standalone Operation: Intuitive high-resolution graphic touchscreen for standalone operation, eliminating
- the need for a PC.
- Channel Configuration: 4 voltage channels, 3 current channels, with convertible voltage channels providing
- 1 voltage and 6 currents.
- High Power Output: High current, high power output of up to 60 Amps/300 VARMS per phase.
- Dynamic Testing Features: Dynamic GPS satellite-synchronized end-to-end testing ability for precision.
- IEC 61850 Compatibility: Capability for IEC 61850 testing to meet industry standards.
Specifications
| FREJA546 / FREJA546N Relay Test System – Specifications | |
|---|---|
| Input Power | |
| Supply | 90 to 264 Volts AC, 1Ø, 50/60 Hz, 1800 VA |
| Outputs | |
| All outputs are independent from sudden changes in line voltage and frequency. All outputs are regulated so changes in load impedance do not affect the output. Each output (VIGEN) module consists of one voltage amplifier and one current amplifier. The voltage amplifier may be converted to a current source. Therefore, one amplifier module may be used to test single-phase current differential relays, including harmonic restraint. | |
| Output Current Sources | |
| The FREJA546 with three VIGEN modules can provide up to six current sources: three high current/high power, and three convertible voltage channels providing lower current/high power. | |
| Per Channel Output | |
| Output Current | Power / Max Voltage |
| 50 mA² | 5 VA / 10.0 V RMS |
| 1 A | 5 VA / 15.0 V RMS |
| 4 A | 200 VA (282 peak) / 50.0 V RMS |
| 15 A | 200 VA (282 peak) / 13.34 V RMS |
| 32 A | 200 VA (282 peak) / 6.25 V RMS |
| 60 A | 319 VA (430 peak) / 5.32 V RMS |
| DC | 200 Watts |
| Duty cycle: 32 A continuous, 60 A for 1.5 seconds or 90 cycles | |
| Three Currents Channels in Parallel | |
| 12 A | 600 VA (848 peak) / 50.0 V RMS |
| 45 A | 600 VA (848 peak) / 13.4 V RMS |
| 96 A | 600 VA (848 peak) / 6.25 V RMS |
| 180 A | 957 VA (1290 peak) / 5.32 V RMS |
| AC Low-level Rogowski Output (Converted Current Channels) | |
| Output Voltage | Max Current |
| 0–2 V RMS | 10 mA |
| 0–10 V RMS | 100 mA |
| 0–40 V RMS | 25 mA |
| Duty cycle: Continuous | |
| Two Current Channels in Series | |
| Compliance voltage doubles: 4 A at 100 V RMS, up to 32 A at 12.5 V RMS | |
| AC Voltage Output | |
| Three voltage sources 0–300 V AC/DC; fourth AC/DC voltage source available as synchronizing or AUX channel. | |
| Output Voltage | Power / Max Current |
| 2 V² | 0.02 VA / 10 mA |
| 30 V | 150 VA / 5 A |
| 150 V | 150 VA / Variable |
| 300 V | 150 VA / 0.5 A |
| DC | 150 Watts |
| Duty cycle: Continuous | |
| Voltage Amplifier in Current Mode | |
| Output Current | Power / Max Voltage |
| 5 A | 150 VA (212 peak) / 30.0 V RMS |
| 15 A | 120 VA / 8.0 V RMS |
| Duty cycle: 5 A continuous, 15 A for 1.5 seconds or 90 cycles | |
| Phase Angle, Voltage and Current | |
| Range | 0.00–359.99° (CCW or CW), or 0.00 to ±180.00° |
| Accuracy | ± 0.02° typical, < 0.1° guaranteed at 50/60 Hz |
| Resolution | 0.001° |
| Frequency | |
| Range | DC: 0.001–1000.000 Hz; transient playback up to 10 kHz (COMTRADE) |
| Resolution | 0.001 Hz |
| Accuracy | 2.5 ppm typical; 25 ppm (0–50 °C) at 50/60 Hz max; AUX: 250 ppm |
| Total Harmonic Distortion | |
| Less than 0.1 % typical, 2 % maximum at 50/60 Hz | |
| Metering | |
| Displays AC/DC volts, amps, time, phase, frequency, ohms, watts, VA, and power factor. Accuracies from 10–100 % range at 25°C ±5°C, 50–60 Hz. | |
| AC Voltage Amplitude | |
| Accuracy | ±0.05 % reading + 0.02 % range typical; ±0.15 % + 0.05 % range max |
| Resolution | 0.01 |
| Ranges | 30, 150, 300 V |
| DC Voltage Amplitude | |
| Accuracy | 0.1 % range typical; 0.25 % range max |
| Resolution | 0.01 |
| Ranges | 30, 150, 300 V |
| AC Low-level Voltage Output | |
| Range | 2 V |
| Accuracy | 0–1 V: 0.5 mV typical / 1 mV guaranteed; 1–2 V: 0.5 mV typical / 2 mV guaranteed |
| Resolution | 0.001 |
| AC Low-level Rogowski Output | |
| Range | 2 V |
| Accuracy | Same as above |
| Ranges | 10, 40 V |
| AC Current Amplitude | |
| Accuracy | ±0.05 % reading + 0.02 % range typical; ±0.15 % + 0.05 % max |
| Resolution | 0.001 / 0.01 |
| Ranges | 32, 60 A |
| AC Low Current | |
| Range | 50 mA |
| Accuracy | ±0.5 mA typical, ±1 mA guaranteed |
| Resolution | 0.0001 |
| DC Current Amplitude | |
| Accuracy | ±0.05 % reading + 0.02 % range typical; ±0.15 % + 0.05 % max |
| Resolution | 0.001 / 0.01 |
| Range | 30 A |
| Convertible Source in AC Current Mode | |
| Accuracy | ±0.05 % reading + 0.02 % range typical; ±0.15 % + 0.05 % or ±12.5 mA |
| Resolution | 0.001 |
| Ranges | 5, 15 A |
| Timer | |
| Range | Seconds: 0.0001–99999.9 (Auto) / Cycles: 0.01–99999.9 (Auto) |
| Accuracy | ±0.001 % of reading typical; ±2 LSD; ±0.005 % from 0–50 °C max |
| Binary Input – Start/Stop/Monitor Gate | |
| Inputs | Up to 10 isolated inputs to monitor relay contacts or trip SCRs |
| Input Rating | Up to 300 V AC/DC |
| Voltage Threshold Range | 5–150 V AC/DC |
| Accuracy | 5–30 V: ±3 V; 31–150 V: ±6 V |
1 review for Megger FREJA 546 Relay Test System
Clear filtersYou must be logged in to post a review.