Megger FREJA 546 Relay Test System

Brand: Megger
SKU: 71840
5.0 1 review
Share

The Megger FREJA 546 is a versatile, portable relay test system for secondary testing of protection relays, with touchscreen and PC control and manual, steady-state and dynamic testing.

  • Secure Purchase
  • Fast Delivery
  • Genuine Guarantee
  • Online Payment

Specifications

FREJA546 / FREJA546N Relay Test System – Specifications
Input Power
Supply 90 to 264 Volts AC, 1Ø, 50/60 Hz, 1800 VA
Outputs
All outputs are independent from sudden changes in line voltage and frequency. All outputs are regulated so changes in load impedance do not affect the output. Each output (VIGEN) module consists of one voltage amplifier and one current amplifier. The voltage amplifier may be converted to a current source. Therefore, one amplifier module may be used to test single-phase current differential relays, including harmonic restraint.
Output Current Sources
The FREJA546 with three VIGEN modules can provide up to six current sources: three high current/high power, and three convertible voltage channels providing lower current/high power.
Per Channel Output
Output Current Power / Max Voltage
50 mA² 5 VA / 10.0 V RMS
1 A 5 VA / 15.0 V RMS
4 A 200 VA (282 peak) / 50.0 V RMS
15 A 200 VA (282 peak) / 13.34 V RMS
32 A 200 VA (282 peak) / 6.25 V RMS
60 A 319 VA (430 peak) / 5.32 V RMS
DC 200 Watts
Duty cycle: 32 A continuous, 60 A for 1.5 seconds or 90 cycles
Three Currents Channels in Parallel
12 A 600 VA (848 peak) / 50.0 V RMS
45 A 600 VA (848 peak) / 13.4 V RMS
96 A 600 VA (848 peak) / 6.25 V RMS
180 A 957 VA (1290 peak) / 5.32 V RMS
AC Low-level Rogowski Output (Converted Current Channels)
Output Voltage Max Current
0–2 V RMS 10 mA
0–10 V RMS 100 mA
0–40 V RMS 25 mA
Duty cycle: Continuous
Two Current Channels in Series
Compliance voltage doubles: 4 A at 100 V RMS, up to 32 A at 12.5 V RMS
AC Voltage Output
Three voltage sources 0–300 V AC/DC; fourth AC/DC voltage source available as synchronizing or AUX channel.
Output Voltage Power / Max Current
2 V² 0.02 VA / 10 mA
30 V 150 VA / 5 A
150 V 150 VA / Variable
300 V 150 VA / 0.5 A
DC 150 Watts
Duty cycle: Continuous
Voltage Amplifier in Current Mode
Output Current Power / Max Voltage
5 A 150 VA (212 peak) / 30.0 V RMS
15 A 120 VA / 8.0 V RMS
Duty cycle: 5 A continuous, 15 A for 1.5 seconds or 90 cycles
Phase Angle, Voltage and Current
Range 0.00–359.99° (CCW or CW), or 0.00 to ±180.00°
Accuracy ± 0.02° typical, < 0.1° guaranteed at 50/60 Hz
Resolution 0.001°
Frequency
Range DC: 0.001–1000.000 Hz; transient playback up to 10 kHz (COMTRADE)
Resolution 0.001 Hz
Accuracy 2.5 ppm typical; 25 ppm (0–50 °C) at 50/60 Hz max; AUX: 250 ppm
Total Harmonic Distortion
Less than 0.1 % typical, 2 % maximum at 50/60 Hz
Metering
Displays AC/DC volts, amps, time, phase, frequency, ohms, watts, VA, and power factor. Accuracies from 10–100 % range at 25°C ±5°C, 50–60 Hz.
AC Voltage Amplitude
Accuracy ±0.05 % reading + 0.02 % range typical; ±0.15 % + 0.05 % range max
Resolution 0.01
Ranges 30, 150, 300 V
DC Voltage Amplitude
Accuracy 0.1 % range typical; 0.25 % range max
Resolution 0.01
Ranges 30, 150, 300 V
AC Low-level Voltage Output
Range 2 V
Accuracy 0–1 V: 0.5 mV typical / 1 mV guaranteed; 1–2 V: 0.5 mV typical / 2 mV guaranteed
Resolution 0.001
AC Low-level Rogowski Output
Range 2 V
Accuracy Same as above
Ranges 10, 40 V
AC Current Amplitude
Accuracy ±0.05 % reading + 0.02 % range typical; ±0.15 % + 0.05 % max
Resolution 0.001 / 0.01
Ranges 32, 60 A
AC Low Current
Range 50 mA
Accuracy ±0.5 mA typical, ±1 mA guaranteed
Resolution 0.0001
DC Current Amplitude
Accuracy ±0.05 % reading + 0.02 % range typical; ±0.15 % + 0.05 % max
Resolution 0.001 / 0.01
Range 30 A
Convertible Source in AC Current Mode
Accuracy ±0.05 % reading + 0.02 % range typical; ±0.15 % + 0.05 % or ±12.5 mA
Resolution 0.001
Ranges 5, 15 A
Timer
Range Seconds: 0.0001–99999.9 (Auto) / Cycles: 0.01–99999.9 (Auto)
Accuracy ±0.001 % of reading typical; ±2 LSD; ±0.005 % from 0–50 °C max
Binary Input – Start/Stop/Monitor Gate
Inputs Up to 10 isolated inputs to monitor relay contacts or trip SCRs
Input Rating Up to 300 V AC/DC
Voltage Threshold Range 5–150 V AC/DC
Accuracy 5–30 V: ±3 V; 31–150 V: ±6 V
5
1 review
1
0
0
0
0

1 review for Megger FREJA 546 Relay Test System

Clear filters
  1. melanie –

    Value for money
    Durability
    Delivery speed

    This relay test system is a valuable tool for our maintenance team.

Add a review