Megger HV test set 110 kV Portable HV test set for DC voltage testing of cables

Short Description:

Buy the MEGGER HV test set 110 kV at a competitive price! Ensure safety and efficiency in your electrical testing with this premium device.

Product purchase

SKU: 92507 Category:
Brand:Megger

Call for Best Price In UAE 00971(04) 447 6031 00971(04) 344 9868

20 People watching this product now!

Terms of sending goods ›

  •  In-stock items are delivered within 2 business days.
  • We are not Supporting COD Payments Terms Outside UAE

Megger HV test set 110 kV

The Megger HV Test Set 110 kV is a high-voltage testing system designed for professionals who need to perform rigorous testing on electrical equipment and insulation. This test set is particularly well-suited for applications in power utilities, industrial environments, and electrical maintenance, where the reliability and safety of high-voltage systems are paramount.

Standard HV test sets are equipped with analog meters. Still, Megger also offers models with digital metering, providing more precise current readings and more accurate voltage settings for enhanced testing accuracy.

Megger HV Test Set 110 kV Key Features

  • Flexible in use thanks to modular design
  • Easy operation and test set-up
  • Low weight
  • Voltage measurement on HV potential
  • Overcurrent tripping and -voltage protection
  • Protective ground circuit
  • Depending on model selected either with analog or digital display of voltage and current

specifications

Megger HV Test Set 110 kV Specifications

Parameter HV Test Set 50 kV HV Test Set 80 kV HV Test Set 110 kV HV Test Set 120 kV
Input Voltage 115 / 230 V, 50 / 60 Hz, 900 VA depending on model selected
Output Voltage (Negative Polarity) 0 … 50 kV DC 0 … 80 kV 0 … 110 kV 0 … 120 kV
Output Current at Max. Voltage 6 mA 5 mA 4 mA 3.5 mA
Overcurrent Trip > 8 mA > 7 mA > 6 mA > 5.5 mA
Analog Versions
Voltage Range (Analog) 0 … 50 kV 0 … 80 kV 0 … 110 kV 0 … 130 kV
Accuracy (Analog Voltage) 1.50% 1.50% 1.50% 1.50%
Current Range (Analog) 0 … 100 µA / 1 mA / 10 mA 0 … 100 µA / 1 mA / 10 mA 0 … 100 µA / 1 mA / 10 mA 0 … 100 µA / 1 mA / 10 mA
Accuracy (Analog Current) 1.50% 1.50% 1.50% 1.50%
Digital Versions (LCD Display)
Voltage Range (Digital) 0 … 130 kV 0 … 130 kV 0 … 130 kV 0 … 130 kV
Resolution (Voltage) 0.1 kV 0.1 kV 0.1 kV 0.1 kV
Accuracy (Digital Voltage) 1% 1% 1% 1%
Current Range (Digital) 0 … 9.999 mA 0 … 9.999 mA 0 … 9.999 mA 0 … 9.999 mA
Resolution (Current) 1 µA 1 µA 1 µA 1 µA
Accuracy (Digital Current) 1% 1% 1% 1%
Operating Temperature -20 °C … +55 °C -20 °C … +55 °C -20 °C … +55 °C -20 °C … +55 °C
Storage Temperature -25 °C … +70 °C -25 °C … +70 °C -25 °C … +70 °C -25 °C … +70 °C
Weight (Control Unit) 13 kg 13 kg 13 kg 13 kg
Weight (HV Unit) 17 kg 18.5 kg 20 kg 20.5 kg
Dimensions (W x H x D) (Control Unit) 37 x 20 x 28 cm 37 x 20 x 28 cm 37 x 20 x 28 cm 37 x 20 x 28 cm
Dimensions (W x H x D) (HV Unit) 21 x 38 x 31 cm 21 x 40 x 31 cm 21 x 42 x 31 cm 21 x 43 x 31 cm

Datasheet