Fluke 1748/30/EUS Power Quality Logger with 60 cm 3,000A iFlex
- 60 cm 3,000A iFlex current probe included
- 16-bit resolution at 10.24 kHz sampling rate
- Measures harmonics up to 50th order
- Stores 20 logging sessions of 4 weeks internally
- Supports 1-phase to 3-phase Aron/Blondel configurations
- Li-ion battery with 4-hour on-battery runtime
- EUS version compliant with regional standards
- Secure Purchase
- Fast Delivery
- Genuine Guarantee
- Online Payment
Description
The Fluke 1748/30/EUS is a premium power quality logger designed for professionals who need to capture and analyze electrical network behavior over extended periods. This EUS-version instrument records voltage, current, frequency, and harmonic distortion across multiple circuit configurations, making it essential for identifying power quality issues in commercial and industrial environments. With its flexible iFlex current probe, users can measure high currents up to 3,000 A without breaking the circuit, while the 16-bit resolution ensures accurate data capture of transient events and harmonic content.
Fluke 1748/30/EUS Key Features
This logger features 16-bit synchronous sampling at 10.24 kHz, synchronized to the mains frequency for precise data acquisition. The device supports a wide range of circuit types including 1-phase, split phase, and three-phase configurations such as delta, wye, and Aron/Blondel connections. Internal flash memory stores up to 20 logging sessions of four weeks each at one-minute intervals, with an additional 500 event markers. The 60 cm iFlex current probe provides safe, non-invasive measurement of currents up to 3,000 A AC, while the user-selectable averaging intervals from 1 second to 30 minutes allow customization for specific monitoring requirements.
- 16-bit resolution at 10.24 kHz sampling rate
- Measures harmonics up to 50th order with interharmonic analysis
- Supports 1-phase through 3-phase Aron/Blondel configurations
- Internal storage for 20 logging sessions of 4 weeks
- 60 cm iFlex probe for 3,000 A AC current measurement
- User-selectable averaging intervals from 1 sec to 30 min
- Li-ion battery with typically 4 hours on-battery runtime
- Internal flash memory, not user-replaceable
Who Needs the Fluke 1748/30/EUS?
Electrical engineers and maintenance technicians will find the Fluke 1748/30/EUS indispensable for troubleshooting power quality issues such as voltage sags, swells, and harmonic distortion. Energy managers can utilize the device to monitor energy consumption patterns and identify opportunities for efficiency improvements through demand interval tracking. Building services contractors rely on this logger for compliance verification and fault diagnosis in complex three-phase systems, while procurement teams appreciate its robust internal memory that eliminates the need for frequent data retrieval visits.
The versatile circuit support makes this suitable for diverse installations, from simple split-phase residential panels to complex three-phase industrial facilities. The ability to measure up to the 50th harmonic and analyze interharmonics provides detailed insight into power quality that basic meters cannot deliver. Maintenance teams working on sensitive equipment can use the flicker analysis features to ensure compliance with standards and prevent premature equipment failure.
Fluke 1748/30/EUS Applications
In industrial settings, the Fluke 1748/30/EUS is used to monitor variable frequency drive (VFD) performance, identifying harmonic distortion that can affect other equipment on the same network. Commercial building managers use the logger for energy audits and to verify power factor correction system effectiveness. Utility companies deploy the device for network analysis and to investigate customer-reported power quality complaints. The logger’s ability to capture transient events such as inrush currents and mains signaling makes it valuable for commissioning new equipment and diagnosing intermittent power issues.
Research and development laboratories benefit from the high-speed sampling rate when testing new power electronic designs, while consulting engineers use the data for load profiling and system optimization studies. The EUS version ensures compliance with regional regulatory requirements, making it suitable for projects with specific certification needs.
Why Buy Fluke 1748/30/EUS from mme-ae?
Mohammad Mahdi Electronics, operating as mme-ae, provides genuine Fluke instruments with full manufacturer warranty and regional support. Our team ensures each power quality logger is factory-calibrated and ready for immediate deployment upon delivery. We stock the complete Fluke range including the 1748/30/EUS EUS version, and our knowledgeable staff can assist with configuration questions and application-specific advice.
When you purchase from mme-ae, you benefit from genuine product assurance, prompt delivery across the UAE, and access to Fluke’s extensive application support resources. Our commitment to customer satisfaction means you receive not just a measurement instrument, but a complete solution with the backing of MME.
Fluke 1748/30/EUS Specifications
| Electrical Specifications | |
| Power Supply | |
| Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit |
| 100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7) | |
| Power consumption | Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter) |
| Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations) |
| Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input |
| Mains power frequency | 50/60 Hz ±15% |
| Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
| On-battery runtime | Typically 4 hours |
| Charging time | < 6 hours |
| Data Acquisition | |
| Resolution | 16-bit synchronous sampling |
| Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency |
| Input signal frequency | 50/60 Hz (42.5 to 69 Hz) |
| Circuit types | 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies) |
| Data storage | Internal flash memory (not user replaceable) |
| Memory size | Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events |
| Basic Interval | |
| Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
| Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
| Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms) |
| Demand Interval (Energy Meter Mode) | |
| Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
| Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off |
| Power Quality Measurements | |
| Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation |
| Averaging interval | 10 min for all parameters 2 hrs (long term Flicker PLT) 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT) |
| Individual harmonics | 2nd to 50th harmonic Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only |
| Interharmonics | 1st to the 50th interharmonic |
| Total harmonic distortion | Calculated on 50 voltage harmonics |
| Events | Voltage: dips, swells, interruptions, current: inrush current 1748: mains signaling, transients (low frequency) |
| Triggered recordings | RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30) |
| Waveform of voltage and current up to 200 ms, 10/12 cycles | |
| Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s | |
| Inrush | RMS profile based on 1/2 cycle RMS steady state triggering |
| Flicker | In accordance with IEC 61000-4-15 and IEEE 1453 |
| Mains signaling | Two user defined frequencies up to 3 kHz |
| PQ Health | Summarizes power quality measurements in one table. Detailed data available for each parameter |
| EN 50160 | Compliance with standard |
| Programmable PQ limits | Enables user defined limits for local standards compliance |
| Standards Compliance | |
| Harmonics | IEC 61000-4-7: Class 1 |
| IEEE 519 (short time and very short time harmonics) | |
| Power quality | IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device) |
| Power | IEEE 1459 |
| Power quality compliance | EN 50160 |
| Safety | General: IEC 61010-1: Pollution Degree 2 |
| Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V | |
| Power Supply: Overvoltage Category IV, Pollution Degree 2 | |
| Li-ion Battery: IEC 62133 | |
| Interfaces | |
| USB-A | File transfer via USB flash drive, firmware updates, max. supply current: 120 mA |
| Wi-Fi (free with product registration) | File transfer and remote control via direct connection or Wi-Fi infrastructure |
| Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or Wi-Fi/BLE adapter, check for availability) |
| USB-mini | Data download device to PC |
| Voltage Inputs | |
| Number of inputs | 4 (3 phases referenced to neutral) |
| Maximum input voltage | 1000 Vrms, CF 1.7 |
| Input impedance | 10 MΩ |
| Bandwidth | 42.5 Hz to 3.5 kHz |
| Scaling | 1:1 and variable |
| Measurement category | 1000 V CAT III/600 V CAT IV |
| Current Inputs | |
| Number of inputs | 4 (3 phases and neutral), mode selected automatically for attached sensor |
| Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8 |
| Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range | |
| Range | 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24 |
| 3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24 | |
| 6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36 | |
| 40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL | |
| Bandwidth | 42.5 Hz – 3.5 kHz |
| Scaling | 1:1 and variable |
| Auxiliary Inputs | |
| Number of inputs | 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously) |
| Input range | 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s |
| Scale factor | Format: mx + b (gain and offset) user configurable |
| Displayed units | User configurable (7 characters, for example, °C, psi, or m/s) |
| Wireless Bluetooth connection (check for availability) | |
| Number of inputs | 2 |
| Supported modules | Fluke Connect® 3000 series |
| Acquisition | 1 reading/s |
| Environmental Specifications | |
| Operating temperature | -25 °C to +50 °C (-13 °F to 122 °F)1 |
| Storage temperature | Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F) |
| Operating humidity | IEC 60721-3-3: 3K6: |
| -25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 % | |
| 40 °C (104 °F): 55 % | |
| 50 °C (122 °F): 35 % | |
| Operating altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
| Storage altitude | 12,000 m |
| Enclosure | IEC 60529: IP50 |
| IEC 60529: IP65 with IP65 rated voltage connector | |
| Vibration | IEC 60721-3-3 / 3M2 |
| Electromagnetic compatibility (EMC) | EN 61326-1: Industrial CISPR 11: Group 1, Class A |
| IEC 61000-6-5 Power station environment | |
| Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) | |
| USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |
| General Specifications | |
| Warranty | Two-years (battery not included) |
| Accessories: one-year | |
| Calibration cycle: two-years | |
| Dimensions | 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in) |
| Weight | Instrument: 1 kg (2.2 lb) |
| Tamper protection | Accept securing cables (max. Φ 6mm) |
| 1Warm up the product to -10 °C (+14 °F) before you power the unit on | |
| i17XX-FLEX1.5KIP Flexible Current Probe Specifications | |
| Measuring range | 1 to 150 A ac/10 to 1500 A ac |
| Probe cable length | 610 mm (24 in) |
| Probe cable diameter | 7.5 mm (0.3 in) |
| Weight | 170 g (0.38 lb) |
| Minimum bending radius | 38 mm (1.5 in) |
| Nondestructive current | 100 kA (50/60 Hz) |
| Temperature coefficient over operating temperature range |
0.05 % of reading/°C (0.028 % of reading/°F) |
| Working voltage | 1000 V CAT III, 600 V CAT IV |
| Output cable length | 2.0 m (6.5 ft) |
| Probe cable material | TPR |
| Weight | 115 g |
| Probe cable material | TPR |
| Coupling material | POM + ABS/PC |
| Output cable | TPR/PVC |
| Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F) |
| Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F) |
| Relative humidity, operating | 15% to 85% non-condensing |
| IP rating | IEC 60529: IP65 |
| Warranty | One-year |
Reviews (0)
You must be logged in to post a review.