Megger FRAX101 Sweep Frequency Response Analyzer

Short Description:

Price drop alert! Buy the Megger FRAX101 in Dubai, UAE, and elevate your testing capabilities with this top-rated instrument. Shop now!

Product purchase

SKU: 92144 Category:
Brand:Megger

Call for Best Price In UAE 00971(04) 447 6031 00971(04) 344 9868

13 People watching this product now!

Terms of sending goods ›

  •  In-stock items are delivered within 2 business days.
  • We are not Supporting COD Payments Terms Outside UAE

Introduction of Megger FRAX101

The Megger FRAX101 Sweep Frequency Response Analyzer is a state-of-the-art diagnostic tool specifically designed for the precise assessment of transformers’ mechanical and electrical integrity. It utilizes Sweep Frequency Response Analysis (SFRA), a proven technique that allows for the detection of potential issues such as winding displacements, core deformation, and other structural faults within transformers that might not be evident through conventional testing methods.

The FRAX series of Sweep Frequency Response Analyzers (SFRA) is designed to detect mechanical and electrical changes in the core and winding assembly of power transformers. For over a decade, major utilities and service companies have relied on the FRA method, which is recognized in international standards. This method is straightforward to execute and captures a unique fingerprint of the transformer, providing valuable insights into its condition.

Megger FRAX101 Key Features

  • Highest accuracy in the industry.
  • High dynamic range to cover all your testing needs
  • Fulfills international standards for SFRA measurements
  • Advanced analysis and decision support built into the software. FRAX 150 with built in PC and touchscreen
  • Imports data from other FRA test sets
  • Wireless communication (FRAX 101)

specifications

Megger FRAX101 Specifications

Specification FRAX 101
Application Field Medium and high-voltage substations and industrial environments
Operating Temperature -20°C to +55°C (-4°F to +131°F)
Storage Temperature -30°C to +70°C (-22°F to +158°F)
Humidity < 95% RH, non-condensing
CE-marking EMC 2004/108/EC, LVD 2006/95/EC
DC Power Supply 11-16 V DC
AC Power Supply
Internal Battery 49 Wh/4.4 Ah (optional)
Instrument Dimensions 410 x 340 x 205 mm (16.1” x 13.4” x 8”)
Transport Case Dimensions 520 x 460 x 220 mm (20.5” x 18.1” x 8.7”)
Instrument Weight 1.95 kg (4.29 lbs) with battery
Case and Accessories Weight 15 kg (33 lbs)
Test Method Sweep frequency (SFRA)
Frequency Range 0.1 Hz – 25 MHz, user selectable
Frequency Resolution 0.01%
Frequency Accuracy 0.01% (measurement error)
Level Resolution 0.001 dB
Number of Points Default 1046, Up to 32,000 points, user selectable
Measurement Time Default 64 s, fast setting, 37 s (20 Hz – 2 MHz)
Points Spacing Logarithmic, linear, or both
Sweep Settings Individual settings for customer defined frequency bands. Linear and logarithmic scale or combination of both
Internal Noise Level < -140 dB
Dynamic Range >150 dB
Inaccuracy ±0.1 dB from +10 dB down to -40 dB, ±0.5 dB from – 41 dB down to -100 dB
IF Bandwidth User selectable, default <10%
USB Yes
Bluetooth Yes
FRAX Software Yes
Standards/Guides Compliance IEC 60076-18, IEEE C57.149, DL/T 911, CIGRE TB 342
Ground Loop Detection Yes

Datasheet

Mme-Pdfs-Image