Megger FRAX 150

The Megger FRAX 150 Sweep Frequency Response Analyzer (SFRA) is a cutting-edge diagnostic instrument designed for comprehensive testing and analysis of power transformers. Utilizing the Sweep Frequency Response Analysis (SFRA) technique, the FRAX 150 is capable of detecting mechanical and electrical changes in the core, windings, and insulation of transformers, providing invaluable insights into their condition and integrity.

The FRAX series functions by applying a sweep frequency test signal to the transformer and analyzing its response. This process generates a unique fingerprint that, when compared to a reference fingerprint of the same transformer, can uncover various faults. These faults include winding deformations and displacements, shorted or open windings, loose or broken clamping structures, core connection issues, core movement, and hoop buckling.

Megger FRAX 150 Key Features

  • Highest accuracy in the industry.
  • High dynamic range to cover all your testing needs
  • Fulfills international standards for SFRA measurements
  • Advanced analysis and decision support built into the software. FRAX 150 with built in PC and touchscreen
  • Imports data from other FRA test sets
  • Continuity control of ground connections

specifications

Megger FRAX 150 Specifications

Specification FRAX 150
Application Field Medium and high-voltage substations and industrial environments
Operating Temperature -5°C to +50°C (23°F to +122°F)
Storage Temperature -30°C to +70°C (-22°F to +158°F)
Humidity < 95% RH, non-condensing
CE Marking EMC 2004/108/EC, LVD 2006/95/EC
DC Power Supply
AC Power Supply 90 – 264 V AC, 47 – 63 Hz
Internal Battery No
Instrument Dimensions (HxWxD) 410 x 340 x 205 mm (16.1” x 13.4” x 8”)
Transport Case Dimensions (HxWxD) No
Instrument Weight 8.5 kg (18.7 lbs)
Case and Accessories Weight Accessories 10 kg (22 lbs)
Test Method Sweep frequency (SFRA)
Frequency Range 0.1 Hz – 25 MHz, user selectable
Frequency Resolution 0.01%
Frequency Accuracy 0.01% (measurement error)
Level Resolution 0.001 dB
Number of Points Default 1046, Up to 32,000 points, user selectable
Measurement Time Default 64 s, fast setting, 37 s (20 Hz – 2 MHz)
Points Spacing Logarithmic, linear, or both
Sweep Settings Individual settings for customer defined frequency bands. Linear and logarithmic scale or combination of both
Internal Noise Level (20 Hz to 2 MHz) < -140 dB
Dynamic Range >150 dB
Inaccuracy ±0.1 dB from +10 dB down to -40 dB ±0.5 dB from – 41 dB down to -100 dB
IF Bandwidth User selectable, default <10%
USB Ports 4 type A, 1 type B
Bluetooth No
FRAX Software Yes
Standards/Guides Compliance IEC 60076-18, IEEE C57.149, DL/T 911, CIGRE TB 342
Ground Loop Detection Yes
Analog Output Channels 1
Compliance Voltage 0.20 – 24 V p-p
Applied Voltage at 50 Ω 0.1 – 12 V p-p
Output Impedance 50 Ω
Analog Input Channels 2
Sampling Rate 100 MS/s
Data Analysis and Management Cross correlation according to DL/T 911 and NCEPRI as well as customizable. Magnitude difference
Data Import Formats Omicron (.fra, .tfra), Doble (.sfra, .sfrx), CIGRE TB342 .xfra, IEC 60076-18 .xml
Data Export Formats CIGRE TB342 .xfra, IEC 60076-18 .xml, Doble .sfra, .csv, .txt
Built-in PC Yes
Operating System Windows embedded
Touchscreen 12”
Memory 1000 records in internal memory
External Storage USB stick

Datasheet