Megger TDM 4540 MV Cable Test and Diagnostics System

Brand: Megger
SKU: 125606
Share

The Megger TDM 4540 is a high-power VLF test and diagnostics system for medium-voltage cables up to 45 kV. Combining VLF (sine and cosine-rectangular), DC and DAC test voltages with tan delta and partial-discharge diagnostics, it tests and assesses long MV cable circuits up to 30 km.

  • Safe Buy
  • Fast Delivery
  • Original Guarantee
  • Online Payment

Specifications

Technical Data (maximum configuration) 25 kV Networks (TDM 4540) 35 kV Networks (TDM 6260)
System option Portable and system-integrated System-integrated
Output voltage
VLF Sine
VLF CR
DC
DAC
0 … 45 kVpeak
0 … 40 kVRMS
0 … ± 45 kV
0 … ± 40 kVpeak
0 … 62 kVpeak
0 … 60 kVRMS
0 … ± 62 kV
0 … ± 60 kVpeak
Frequency
VLF Sinusoidal/rectangular
VLF cosine-rectangular (VLF CR)
Damped AC (DAC)
0.01 … 0.1 Hz (automatic frequency adaption)
0.1 Hz
20 … 500 Hz
Output current 12 mA 23 mA
Leakage current measurement 0 … 20 mA, resolution 10 µA 0 … 20 mA, resolution 10 µA
Testable capacity
VLF Sine
VLF CR
DAC
0.6 µF @ 0.1 Hz
10 µF max
5 µF @ 0.1 Hz (40 kVRMS)
5.6 µF @ 0.1 Hz (36 kVRMS)
10 µF @ 0.1 Hz (18 kVRMS)
5 µF (40 kVpeak)
1 µF @ 0.1 Hz
10 µF max
4.4 µF @ 0.1 Hz (60 kVRMS)
7.8 µF @ 0.1 Hz (36 kVRMS)
10 µF @ 0.1 Hz (18 kVRMS)
4.6 µF (60 kVpeak)
Sheath testing / pinpointing 0 to 5 / 10 / 20 kV 0 to 5 / 10 / 20 kV
Internal tan delta (option)
Range
Accuracy
Resolution
10⁻³ to 10⁰
10⁻³
10⁻⁴
10⁻⁴ to 10⁰
10⁻⁴
10⁻⁵ / 10⁻⁶
Partial discharge option Available
Control Portable: via VLF unit, PD measurement via laptop System-integrated: via laptop or Primeon/Centrix control-unit
Duty cycle Continuous
Weight / dimensions Depending on configuration
Operating temperature -20 °C … +55 °C
Storage temperature -20 °C … +70 °C
0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Megger TDM 4540 MV Cable Test and Diagnostics System”