Fluke 1742, 1746 and 1748 Three-Phase Power Quality Loggers
- Accurate power quality logging for 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, and more.
- 16-bit synchronous sampling and 10.24 kHz sampling frequency.
- Internal flash memory for up to 20 logging sessions.
- User-selectable averaging intervals and demand intervals.
- Measures power quality parameters, including THD V, THD A, and flicker.
- Customer-replaceable Li-ion battery with up to 4 hours on-battery runtime.
- IEC 61000-4-30 compliant.
- Secure Purchase
- Fast Delivery
- Genuine Guarantee
- Online Payment
Description
The Fluke 1742, 1746, and 1748 Three-Phase Power Quality Loggers are designed to provide accurate and reliable power quality measurements for a wide range of applications. With 16-bit synchronous sampling and a sampling frequency of 10.24 kHz, these loggers can capture even the most subtle changes in power quality.
These loggers are ideal for use in industrial, commercial, and residential settings, and can be used to measure a variety of power quality parameters, including THD V, THD A, and flicker. The internal flash memory allows for up to 20 logging sessions, and the user-selectable averaging intervals and demand intervals make it easy to customize the logging process to meet your specific needs.
Fluke 1742 Key Features
The Fluke 1742 Three-Phase Power Quality Logger features a customer-replaceable Li-ion battery with up to 4 hours on-battery runtime, making it ideal for use in remote or hard-to-reach locations.
- Power Supply: 100 V to 500 V using safety plug input when powering from the measurement circuit, 100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7)
- Power Consumption: Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter)
- Efficiency: ≥ 68.2% (in accordance with energy efficiency regulations)
- Maximum No-Load Consumption: < 0.3 W only when powered using IEC 60320 input
- Mains Power Frequency: 50/60 Hz ±15%
- Battery: Li-ion 3.7 V, 9.25 Wh, customer-replaceable
- On-Battery Runtime: Typically 4 hours
- Charging Time: < 6 hours
- Data Acquisition Resolution: 16-bit synchronous sampling
- Sampling Frequency: 10.24 kHz at 50/60 Hz, synchronized to mains frequency
- Input Signal Frequency: 50/60 Hz (42.5 to 69 Hz)
- Circuit Types: 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φ wye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies)
Who Needs the Fluke 1742?
The Fluke 1742 Three-Phase Power Quality Logger is ideal for use in a wide range of applications, including industrial, commercial, and residential settings. It is designed to provide accurate and reliable power quality measurements, making it an essential tool for anyone who needs to monitor and analyze power quality.
Whether you are a technician, engineer, or maintenance professional, the Fluke 1742 is a valuable asset that can help you to identify and troubleshoot power quality issues, and to ensure that your equipment is running at optimal levels.
Fluke 1742 Applications
- Industrial Power Quality Monitoring: The Fluke 1742 is ideal for use in industrial settings, where power quality is critical to the operation of equipment and machinery.
- Commercial Power Quality Monitoring: The Fluke 1742 is also suitable for use in commercial settings, such as offices, retail stores, and restaurants.
- Residential Power Quality Monitoring: The Fluke 1742 can be used to monitor power quality in residential settings, such as homes and apartments.
- Power Quality Analysis: The Fluke 1742 can be used to analyze power quality data, and to identify trends and patterns in power quality.
- Load Studies: The Fluke 1742 can be used to conduct load studies, which can help to identify areas where power quality is being affected.
- Energy Efficiency Monitoring: The Fluke 1742 can be used to monitor energy efficiency, and to identify areas where energy is being wasted.
Why Buy Fluke 1742 from mme-ae?
The Fluke 1742 Three-Phase Power Quality Logger is a high-quality product that is designed to provide accurate and reliable power quality measurements. At mme-ae, we offer a wide range of power quality monitoring solutions, including the Fluke 1742, and our experienced team is always available to provide expert advice and support.
Whether you are looking for a reliable power quality logger or a comprehensive power quality monitoring solution, we have the expertise and the products to meet your needs. Contact us today to learn more about the Fluke 1742 and how it can benefit your business.
Fluke 1742 Specifications
| Electrical Specifications | |
| Power Supply | |
| Voltage range | 100 V to 500 V using safety plug input when powering from the measurement circuit |
| 100 V to 240 V MA-C8 and using standard power cord (IEC 60320 C7) | |
| Power consumption | Maximum 50 VA (max. 15 VA when powered using MA-C8 adapter) |
| Efficiency | ≥ 68.2% (in accordance with energy efficiency regulations) |
| Maximum no-load consumption | < 0.3 W only when powered using IEC 60320 input |
| Mains power frequency | 50/60 Hz ±15% |
| Battery | Li-ion 3.7 V, 9.25 Wh, customer-replaceable |
| On-battery runtime | Typically 4 hours |
| Charging time | < 6 hours |
| Data Acquisition | |
| Resolution | 16-bit synchronous sampling |
| Sampling frequency | 10.24 kHz at 50/60 Hz, synchronized to mains frequency |
| Input signal frequency | 50/60 Hz (42.5 to 69 Hz) |
| Circuit types | 1-Φ, 1-Φ IT, split phase, 3-Φ delta, 3-Φ wye, 3-Φwye IT, 3-Φ wye balanced, 3-Φ Aron/Blondel (2-element delta), 3-Φ delta open leg, currents only (load studies) |
| Data storage | Internal flash memory (not user replaceable) |
| Memory size | Typical 20 logging sessions of 4 weeks with 1-minute intervals and 500 events |
| Basic Interval | |
| Measured parameters | Voltage, current, aux, frequency, THD V, THD A, power, power factor, fundamental power, DPF, energy |
| Averaging interval | User selectable: 1 sec, 5 sec, 10 sec, 30 sec, 1 min, 5 min, 10 min, 15 min, 30 min |
| Averaging time min/max values | Voltage, Current: Full cycle RMS updated every half cycle (URMS1/2 according to IEC61000-4-30 Aux, Power: 200ms) |
| Demand Interval (Energy Meter Mode) | |
| Measured parameters | Energy (Wh, varh, VAh), PF, maximum demand, cost of energy |
| Interval | User selectable: 5 min, 10 min, 15 min, 20 min, 30 min, off |
| Power Quality Measurements | |
| Measured parameter | Voltage, frequency, unbalance, voltage harmonics, THD V, current, harmonics, THD A, TDD, voltage interharmonics, TID V, current interharmonics, TID A, Flicker, Mains Signaling, under/over deviation |
| Averaging interval | 10 min for all parameters 2 hrs (long term Flicker PLT) 150/180 cycles (3 s) for harmonics (requires software license IEEE519/REPORT) |
| Individual harmonics | 2nd to 50th harmonic Grouping according to IEC 61000-4-7 user configurable depending on application: Sub-grouped (harmonics + interharmonics), grouped or harmonic bins only |
| Interharmonics | 1st to the 50th interharmonic |
| Total harmonic distortion | Calculated on 50 voltage harmonics |
| Events | Voltage: dips, swells, interruptions, current: inrush current 1748: mains signaling, transients (low frequency) |
| Triggered recordings | RMS profile: Full cycle RMS updated every half cycle of voltage and current up to 11 s (URMS1/2 according to IEC 61000-4-30) |
| Waveform of voltage and current up to 200 ms, 10/12 cycles | |
| Mains signaling: 10/12 cycle RMS recording of the configured frequencies up to 120s | |
| Inrush | RMS profile based on 1/2 cycle RMS steady state triggering |
| Flicker | In accordance with IEC 61000-4-15 and IEEE 1453 |
| Mains signaling | Two user defined frequencies up to 3 kHz |
| PQ Health | Summarizes power quality measurements in one table. Detailed data available for each parameter |
| EN 50160 | Compliance with standard |
| Programmable PQ limits | Enables user defined limits for local standards compliance |
| Standards Compliance | |
| Harmonics | IEC 61000-4-7: Class 1 |
| IEEE 519 (short time and very short time harmonics) | |
| Power quality | IEC 61000-4-30 Class A, IEC 62586-1, IEC 62586-2 (PQI-A-PI device) |
| Power | IEEE 1459 |
| Power quality compliance | EN 50160 |
| Safety | General: IEC 61010-1: Pollution Degree 2 |
| Measurement: IEC 61010-2-033: CAT IV 600 V / CAT III 1000 V | |
| Power Supply: Overvoltage Category IV, Pollution Degree 2 | |
| Li-ion Battery: IEC 62133 | |
| Interfaces | |
| USB-A | File transfer via USB flash drive, firmware updates, max. supply current: 120 mA |
| Wi-Fi (free with product registration) | File transfer and remote control via direct connection or Wi-Fi infrastructure |
| Bluetooth | Read auxiliary measurement data from Fluke Connect® 3000 series modules (requires supported USB to BLE or Wi-Fi/BLE adapter, check for availability) |
| USB-mini | Data download device to PC |
| Voltage Inputs | |
| Number of inputs | 4 (3 phases referenced to neutral) |
| Maximum input voltage | 1000 Vrms, CF 1.7 |
| Input impedance | 10 MΩ |
| Bandwidth | 42.5 Hz to 3.5 kHz |
| Scaling | 1:1 and variable |
| Measurement category | 1000 V CAT III/600 V CAT IV |
| Current Inputs | |
| Number of inputs | 4 (3 phases and neutral), mode selected automatically for attached sensor |
| Input voltage | Clamp input: 500 mVrms/50 mVrms; CF 2.8 |
| Rogowski coil input: 150 mVrms/15 mVrms at 50 Hz, 180 mVrms/18 mVrms at 60 Hz; CF 4 all at nominal probe range | |
| Range | 1 A to 150 A/10 A to 1500 A with thin flexible current probe i17XX-flex1500 IP 24 |
| 3 A to 300 A/30 A to 3000 A with thin flexible current probe i17XX-flex3000 IP 24 | |
| 6 A to 600 A/60 A to 6000 A with thin flexible current probe i17XX-flex6000 IP 36 | |
| 40 mA to 4 A/0.4 A to 40 A with 40 A clamp i40s-EL | |
| Bandwidth | 42.5 Hz – 3.5 kHz |
| Scaling | 1:1 and variable |
| Auxiliary Inputs | |
| Number of inputs | 2 (Analog with auxiliary adapter, or up to 2 BLE devices simultaneously) |
| Input range | 0 to ± 10 V dc, or 0 to ± 1000 V dc (with optional adapter), 1 reading/s |
| Scale factor | Format: mx + b (gain and offset) user configurable |
| Displayed units | User configurable (7 characters, for example, °C, psi, or m/s) |
| Wireless Bluetooth connection (check for availability) | |
| Number of inputs | 2 |
| Supported modules | Fluke Connect® 3000 series |
| Acquisition | 1 reading/s |
| Environmental Specifications | |
| Operating temperature | -25 °C to +50 °C (-13 °F to 122 °F)1 |
| Storage temperature | Without battery: -25 °C to +60 °C (-13 °F to 140 °F), with battery: -20 °C to +50 °C (−4 °F to 122 °F) |
| Operating humidity | IEC 60721-3-3: 3K6: |
| -25 °C to +30 °C (-13 °F to +86 °F): ≤ 100 % | |
| 40 °C (104 °F): 55 % | |
| 50 °C (122 °F): 35 % | |
| Operating altitude | 2000 m (up to 4000 m derate to 1000 V CAT II/600 V CAT III/300 V CAT IV) |
| Storage altitude | 12,000 m |
| Enclosure | IEC 60529: IP50 |
| IEC 60529: IP65 with IP65 rated voltage connector | |
| Vibration | IEC 60721-3-3 / 3M2 |
| Electromagnetic compatibility (EMC) | EN 61326-1: Industrial CISPR 11: Group 1, Class A |
| IEC 61000-6-5 Power station environment | |
| Korea (KCC): Class A Equipment (industrial broadcasting and communication equipment) | |
| USA (FCC): 47 CFR 15 subpart B. This product is considered an exempt device per clause 15.103 | |
| General Specifications | |
| Warranty | Two-years (battery not included) |
| Accessories: one-year | |
| Calibration cycle: two-years | |
| Dimensions | 23.0 cm x 18.0 cm x 5.4 cm (9.1 in x 7.1 in x 2.1 in) |
| Weight | Instrument: 1 kg (2.2 lb) |
| Tamper protection | Accept securing cables (max. Φ 6mm) |
| 1Warm up the product to -10 °C (+14 °F) before you power the unit on | |
| i17XX-FLEX1.5KIP Flexible Current Probe Specifications | |
| Measuring range | 1 to 150 A ac/10 to 1500 A ac |
| Probe cable length | 610 mm (24 in) |
| Probe cable diameter | 7.5 mm (0.3 in) |
| Weight | 170 g (0.38 lb) |
| Minimum bending radius | 38 mm (1.5 in) |
| Nondestructive current | 100 kA (50/60 Hz) |
| Temperature coefficient over operating temperature range |
0.05 % of reading/°C (0.028 % of reading/°F) |
| Working voltage | 1000 V CAT III, 600 V CAT IV |
| Output cable length | 2.0 m (6.5 ft) |
| Probe cable material | TPR |
| Weight | 115 g |
| Probe cable material | TPR |
| Coupling material | POM + ABS/PC |
| Output cable | TPR/PVC |
| Operating temperature | -20 °C to +70 °C (-4 °F to 158 °F) temperature of conductor under test shall not exceed 80 °C (176 °F) |
| Temperature, non-operating | -40 °C to +80 °C (-40 °F to 176 °F) |
| Relative humidity, operating | 15% to 85% non-condensing |
| IP rating | IEC 60529: IP65 |
| Warranty | One-year |
Datasheet
Datasheet
User Manual
User Manual
Reviews (0)
You must be logged in to post a review.
Bench Multimeters