Amprobe ACDC-100 TRMS 1000 A AC/DC Clamp Meter

Short Description:

The Amprobe ACDC-100 TRMS 1000 A AC/DC Clamp Meter stands out as a high-quality, multifunctional tool that meets the needs of electricians and technicians, providing a balance of performance, durability, and user-friendly features.

Product purchase

SKU: 94381-1-1 Category:
Brand:Amprobe

Call for Best Price In UAE 00971(04) 447 6031 00971(04) 344 9868

18 People watching this product now!

Terms of sending goods ›

  •  In-stock items are delivered within 2 business days.
  • We are not Supporting COD Payments Terms Outside UAE

Amprobe ACDC 100 TRMS

The Amprobe ACDC-100 TRMS 1000 A AC/DC Clamp Meter is a versatile and robust tool designed for electrical professionals requiring accurate AC and DC currents measurements. This clamp meter is particularly noted for its true RMS capability, which allows it to provide accurate readings even in non-sinusoidal waveforms. This makes it ideal for a variety of applications in industrial and commercial settings.

Key Features

Measurement Capabilities

  • AC Current: Measures up to 800 A
  • DC Current: Measures up to 1000 A
  • AC/DC Voltage: Ranges from 400.0 mV to 600 V
  • Resistance: Up to 40 MΩ
  • Capacitance: Up to 3000 µF
  • Continuity Testing: Equipped with a beeper for quick identification of continuity

Design and Ergonomics

  • Jaw Size: The large jaws can accommodate conductors up to 2 inches (50 mm) in diameter, allowing for easy clamping around various wire sizes.
  • Ergonomic Design: The clamp meter features a rubber over-molded casing for better grip and durability, enhancing user comfort during prolonged use.

Additional Features

  • Data Hold Function: Freezes the current reading on the display for easy note-taking.
  • Relative Zeroing Mode: Allows users to set a reference point for measurements, enhancing accuracy in comparative readings.
  • Auto Power Off: Automatically turns off the device after a period of inactivity to conserve battery life.
  • MAX Capturing Function: Captures inrush current measurements, useful for analyzing equipment startup currents.

Datasheet

Datasheet

Datasheet

Specifications

General Specifications
Display 3-3/4 digits 4000 counts LCD display
Update Rate 3 per second nominal
Polarity Automatic
Low Battery Below approx. 2.4V
Operating Temperature 0C to 40C
Relative Humidity Maximum relative humidity 80% for temperature up to 31C, decreasing linearly to 50% relative humidity at 40C
Altitude Operating below 2000m
Storage Temperature -20C to 60C, < 80% R.H. (with battery removed)
Temperature Coefficient nominal 0.15 x (specified accuracy)/ C @(0C -18C or 28C -40C), or otherwise specified
Sensing True RMS
Safety Meets EN61010-1:2001; IEC61010-2-032(2002), EN61010-2-032(2002), UL61010B-2-032(2003) Category III 600 Volts AC & DC.
Transient protection 6.5kV (1.2/50μs surge) for all models
Pollution degree 2
E.M.C. Meets EN61326-1
Overload Protections
Clamp-on jaws DC 1000A or AC 800A rms continuous + & COM terminals (all functions) : 600VDC/VAC rms
Power Supply standard 1.5V AAA Size (NEDA 24G or IEC R03) battery X 2; or 1.5V AAA Size (NEDA 24A or IEC LR03) alkaline battery X 2
Power Consumption typical 11mA for ACA/DCA and 2.9mA for other functions
APO Timing Idle for 30 minutes
APO Consumption typical 190μA
Dimension L227mm X W78mm X H40mm
Weight 290 gm approx
Jaw opening & Conductor diameter 50mm max
Electrical Specifications Accuracy is ±(% reading digits + number of digits) or otherwise specified, at 23? ± 5? & less than 75% R.H.
DC Voltage
400.0 mV 0.3% + 3d
4.000V, 40.00V, 400.0V 0.5% + 3d
600V 1.0% + 4d
NMRR : >50dB @ 50/60Hz
CMRR : >120dB @ DC, 50/60Hz, Rs=1kΩ
Input Impedance : 10MΩ, 30pF nominal (1000MΩ for 400.0mV range)
AC Voltage
50Hz ~ 500Hz 400.0mV 1) 4.0% + 4d
50Hz ~ 60Hz 4.000V, 40.00V, 400.0V 1.0% + 4d
60Hz ~ 500Hz 4.000V, 40.00V, 400.0V 1.5% + 4d
50Hz ~ 500Hz 600V 2.0% + 4d
CMRR : >60dB @ DC to 60Hz, Rs=1kΩ
Input Impedance: 10MΩ, 30pF nominal
ACDC-100 TRMS Crest Factor: < 1.6 : 1 at full scale & < 3.2 : 1 at half scale
1) Selection by RANGE button manually, and is specified AC 60mV and up
Resistance
400.0Ω 0.8% + 6d
4.000kΩ, 40.00kΩ, 400.0kΩ 0.6% + 4d
4.000MΩ 1.0% + 4d
40.00MΩ 2.0% + 4d
Open Circuit Voltage : 0.4VDC typical
Audible Continuity Tester
Open Circuit Voltage: 0.4VDC typical
Range: 400.0Ω; Accuracy: 1.5% + 6d
Audible threshold: between 10Ω and 120Ω.
Diode Tester
Open Circuit Voltage Test Current (Typical)
< 1.6 VDC 0.4mA
Capacitance
500.0nF, 5.000μF, 50.00μF, 3.5% + 6d2) 3)
500.0μF, 3000μF 1)
1) Additional 50.00nF range accuracy is not specified
2) Accuracies with film capacitor or better
3) Specified with battery voltage above 2.8V (approximately half full battery). Accuracy decreases gradually to 12% at low battery
warning voltage of approximately 2.4V
DC Current (Clamp-on)
400.0A 0.0A ~ 400.0A 1.5% + 4d 1) 2)
1000A 400A ~ 800A 1.5% + 4d 1) 2)
800A ~ 900A 2.0% + 4d 1) 2)
900A ~ 1000A 5.0% + 30d 1) 2)
1) Induced error from adjacent current-carrying conductor: < 0.01A/A
2) Δ Zero mode must be applied to zero the unit before measurement to ensure accuracy. This is particularly important below 20A.
AC Current (Clamp-on)
400.0A
15Hz ~ 40Hz 2.0% + 5d 1) 2) 3)
40Hz ~ 200Hz 1.5% + 5d 1) 2)
200Hz ~ 400Hz @ <50A 4) 1.5% + 5d 1) 2)
400Hz ~ 1kHz @ <50A 4) 2.0% + 5d 1) 2)
800A
15Hz ~ 40Hz @ 400A ~ 600A 2.0% + 5d 1) 2) 3)
40Hz ~ 100Hz @ 400A ~ 600A 1.5% + 4d 1) 2)
15Hz ~ 60Hz @ 600A ~ 800A 5.0% + 30d 1) 2)
1) Induced error from adjacent current-carrying conductor: < 0.01A/A
2) ACDC-100 TRMS crest Factor: < 1.6 : 1 at full scale & < 3.2 : 1 at half scale
3) 4.0% + 5d for ACDC-100 TRMS
4) Accuracy is specified at <50A in this frequency bandwidth due to limited calibrator output capability for testing