Sbs Arga Battery Monitor Panel Mount
Short Description:
SBS Arga Battery Monitor Panel Mount Key Features
- Adjustable alarm threshold set points
- High/low battery voltage alarms
- ± Ground fault detection with alarm
- AC charger power loss
- High accuracy ± 0.2 VDC
- Open cell / AC charger malfunction alarm
- Electroswitch Battery Monitor
Call for Best Price In UAE 00971(04) 447 6031 00971(04) 344 9868
- In-stock items are delivered within 2 business days.
- We are not Supporting COD Payments Terms Outside UAE
Buy SBS Arga Battery Monitor Panel Mount
The SBS Arga Battery Monitor Panel Mount from Electroswitch monitors battery voltage and ground fault detection for DC systems. A LED display identifies alarm conditions in addition to audible alarms. Easily calibrate and set alarm thresholds through the front panel menu.
Alarm functions: battery voltage, ground fault detection, AC power loss, ripple voltage, ripple current, high impedance, and predictive corrosion detection.
Remote monitoring and reporting are ideal for multiple and distant locations. The Arga Battery Monitor Panel Mount supports Serial DNP3.0, Modbus, and RS485 communications.
Contact our experts for more information about the SBS Arga Battery Monitor price. As a well-known distributor, MMElectronic is pleased to meet all of your requirements for battery testers by providing the greatest international brands at cost-effective pricing.
SBS Arga Battery Monitor Panel Mount Specifications
SBS Arga Battery Tester has battery input for 125, 250 and 48 V batteries; 50–180 VDC, 3VA (for 125 V battery), 100–360 VDC, 5VA (for 250 V battery), and 36–72 VDC, 3VA (for 48 V battery).
- Battery Input:
50–180 VDC, 3VA (for 125 V battery)
100–360 VDC, 5VA (for 250 V battery)
36–72 VDC, 3VA (for 48 V battery) - Ground Resistors:
30.83 KΩ ± 1% from each bus to ground (for 125 V battery)
60.50 KΩ ± 1% from each bus to ground (for 250 V battery)
15 KΩ ± 1% from each bust to ground (for 48 V battery) - Voltage Indication : 0 to ± 199.9 VDC in 0.6″ bright red LED digits and decimal point. Accuracy is ± 0.2 VDC (125 VDC model).
- Alarms :
Alarm relays are Form C contacts
Relay 1: + ground fault
Relay 2: – ground fault
Relay 3: high battery voltage
Relay 4: low battery voltage, open battery, loss of AC to the charger - Standard Outputs Digital: DNP3.0, Modbus , Analog: 4~20 mA
- Contact Rating 2A at 120 VAC or 28 VDC, 25 mA at 150 VDC
- Voltages: 24 VDC, 48 VDC, 125 VDC, 250 VDC
- Standard Part Numbers :
25-1000-125A for 125 VDC installations
25-1000-250A for 250 VDC installations
25-1000-48A for 48 VDC installations
For 19″ Rack (single meter)
15-1000-125A-1 for 125 VDC installations
15-1000-250A-1 for 250 VDC installations
15-1000-48A for 48 VDC installations - Size : 4.33″ W x 4.33” H