SBS Arga Battery Monitor Portable

(1 customer review)

Short Description:

Sbs Arga Battery Monitor Portable Key Features

  • Adjustable alarm threshold set points
  • High / low battery voltage alarms
  • ± Ground fault detection with alarm
  • AC charger power loss
  • High accuracy ± 0.2 VDC
  • Open cell alarm
Product purchase
SKU: 5817
Brand:SBS

Call for Best Price In UAE 00971(04) 447 6031 00971(04) 344 9868

20 People watching this product now!
Terms of sending goods ›
  •  In-stock items are delivered within 2 business days.
  • We are not Supporting COD Payments Terms Outside UAE
Description

Buy SBS Arga Battery Monitor Portable

The Electroswitch Arga Battery Monitor Portable is intended to be portable and self-contained for monitoring battery voltage, ground fault detection, and alarm outputs in the field. In addition to auditory alerts, an LED display identifies alarm circumstances. The front panel menu makes it simple to calibrate and set alarm thresholds.

Battery voltage, ground fault detection, AC power loss, ripple voltage, ripple current, high impedance, and predicted corrosion detection are all alarm functions.

Remote monitoring and reporting are ideal for monitoring many remote locations. The Arga Battery Monitor Portable supports serial DNP3.0, Modbus, and RS485 communications.

SBS Arga Battery Monitor Portable Specifications

SBS Arga Battery Tester has battery input for 125, 250 and 48 V batteries; 50–180 VDC, 3VA (for 125 V battery), 100–360 VDC, 5VA (for 250 V battery), and 36–72 VDC, 3VA (for 48 V battery)

  • Battery Input:
    • 50–180 VDC, 3VA (for 125 V battery)
    • 100–360 VDC, 5VA (for 250 V battery)
    • 36–72 VDC, 3VA (for 48 V battery)
  • Ground Resistors:
    • 30.83 KΩ ± 1% from each bus to ground (for 125 V battery)
    • 60.50 KΩ ± 1% from each bus to ground (for 250 V battery)
    • 15 KΩ ± 1% from each bust to ground (for 48 V battery)
  • Voltage Indication : 0 to ± 199.9 VDC in 0.6″ bright red LED digits and decimal point. Accuracy is ± 0.2 VDC (125 VDC model).
  • Alarms:
    • Alarm relays are Form C contacts
    • Relay 1: + ground fault
    • Relay 2: – ground fault
    • Relay 3: high battery voltage
    • Relay 4: low battery voltage, open battery, loss of AC to the charger
  • Standard Outputs
    • Digital: DNP3.0, Modbus
    • Analog: 4~20 mA
  • Contact Rating: 2A at 120 VAC or 28 VDC, 25 mA at 150 VDC
  • Voltages: 24 VDC, 48 VDC, 125 VDC, 250 VDC
  • Standard Part Numbers:
    • 50-1000-125A for 125 VDC installations
    • 50-1000-250A for 250 VDC installations
    • 50-1000-48A for 48 VDC installations

MME-AE has the SBS Arga Portable battery tester waiting for you—experience peak performance and prevent downtime with every test!

Data Sheet

Data Sheet

Data Sheet

Reviews (1)
5
1 review
1
0
0
0
0

1 review for SBS Arga Battery Monitor Portable

Clear filters
  1. Liam

    Very great device

Add a review