The Model MEGGER 830220-1 CABLE PHASING METER offers a safe and quick method of measuring voltage and determining phase rotation of underground distribution systems using the capacitance test point of elbow connectors.
Call for Best Price In UAE 00971(04) 447 6031 00971(04) 344 9868
We are not Supporting COD Payments Terms Outside UAE
MEGGER 830220-1 Cable Phasing Meter
The Model 830220-1 Cable Phasing Meter offers a safe and quick method of measuring voltage and determining phase rotation of underground distribution systems using the capacitance test point of elbow connectors. Most manufacturers of high-voltage cable terminators incorporate capacitance test points into their elbow connectors. These test points are designed for measuring purposes.
Key Features of the 830220-1 Cable Phasing Meter
- The 830220-1 is capable of accurately measuring voltage levels within underground distribution systems. This feature is crucial for ensuring that voltage levels are appropriate for safety and efficiency before any maintenance or installation work is performed.
- Determining phase rotation is essential for the correct installation and troubleshooting of electrical systems. The 830220-1 provides a straightforward method for assessing the phase rotation using the capacitance test points. This helps prevent issues related to incorrect phasing, which can lead to equipment damage and safety hazards.
MEGGER 830220-1 Specifications
- Voltage : Ranges0 to 15 kV0 to 30 kV
- Accuracy : ±8% (exclusive of tap capacitance variations)
- Tap Capacitance Setting : 0.4 to 3.0 pF continuous per channel
- Frequency : 50 or 60 Hz
- Instrument : 5.5 H x 2.5 W x 7.5 D in.(140 H x 60 W x 190 D mm)
- Case : 6 H x 6 W x 9 D in.(150 H x 150 H x 230 D mm)
- Instrument:4 lb (2 kg)
- Shipping:6 lb (3 kg)
You must be logged in to post a review.
SPECIFICATIONS
Specification | Details |
---|---|
Power Source | Four AA batteries (300 hours of continuous operation) |
Voltage Ranges | 0 to 15 kV, 0 to 30 kV |
Accuracy | ±8% (exclusive of tap capacitance variations) |
Tap Capacitance Setting | 0.4 to 3.0 pF continuous per channel |
Frequency | 50 or 60 Hz |
Dimensions – Instrument | 5.5 H x 2.5 W x 7.5 D in. (140 H x 60 W x 190 D mm) |
Dimensions – Case | 6 H x 6 W x 9 D in. (150 H x 150 H x 230 D mm) |
Weight – Instrument | 4 lb (2 kg) |
Weight – Shipping | 6 lb (3 kg) |