Megger SDRM202 Resistance Measurement Accessory

Brand: Megger
SKU: 4976
Share

The Megger SDRM202 is a static and dynamic resistance measurement (SRM/DRM) accessory for the TM1800, TM1700 and EGIL breaker analysers. Injecting up to 500 A DC, it measures main-contact resistance during breaker operation to reveal arcing-contact wear without dismantling the breaker.

  • Safe Buy
  • Fast Delivery
  • Original Guarantee
  • Online Payment

Specifications

Megger SDRM202 – Technical Specifications
Environmental Specifications
Application Field Intended for use in high-voltage substations and industrial environments
Installation Category CAT I
Pollution Degree 2
Operating Temperature -20°C to +50°C (-4°F to +122°F)
Storage & Transport Temperature -40°C to +70°C (-40°F to +158°F)
Vibration IEC 60068-2-6, 2 g for 5–500 Hz
Shock (Non-operating) IEC 60068-2-27, 30 g half-sine, 11 ms
Degree of Protection SDRM202 (Box) and SDRM Cable interconnected: IP43
Humidity 5% – 95% RH, non-condensing
CE Marking LVD: 2006/95/EC
EMC: 2004/108/EC
General Specifications
Power Inlet 24 V / 2.5 A
Voltage 24 V DC (max), 21 V DC (min)
Current 2.5 A (max, 50% intermittence)
Dimensions 160 × 240 × 90 mm (6.3” × 9.4” × 3.5”) excluding binding posts
Weight 1.8 kg (4 lbs)
4.3 kg (9.5 lbs) including current cables
Total with transport case and accessories: 11 kg (24 lbs)
SDRM Cable 0.2 m (0.7 ft), 0.7 kg (1.5 lbs)
Extension Cable 7.5 m (24.5 ft), 0.7 kg (1.5 lbs)
SDRM202 – Terminals
CURRENT OUTPUT Terminals (1 and 2) Open Circuit Voltage: 2.5 V DC (max)
Short Circuit Current (Instantaneous): 500 A DC
Short Circuit Current (After 2 seconds): 150 A ±10%
Minimum Current with Cables (Instantaneous): 200 A DC
Minimum Current with Cables (After 1 second): 140 A DC
Overvoltage Protection: 45 V between terminals and ground
Not to be connected to circuits generating peak power pulse above 1500 W (10/1000 µs)
SDRM Cable – Terminals
Compatible Equipment TM1800, TM1700, TM1600, EGIL
ANALOG INPUT Terminals (I1 and I2) Max Voltage: 12 V DC
Voltage: 10 V/250 A (TM1800, TM1700, EGIL); 1 V/250 A (TM1600)
Short Circuit Current (max): 100 mA
SRM Inaccuracy TM1800, TM1700, TM1600: ±1% ±1 μΩ
EGIL: ±2% ±2 μΩ
DRM OUTPUT Terminal / TRIG Terminal
Voltage 60 V DC (max)
Trigger Threshold 9 V (min) – 10 V (max)
Trigger Current at Threshold 40 mA (max)
1 review