Amprobe AC50A
The Amprobe AC50A AC Leakage Clamp Meter is a specialized tool designed for electricians, maintenance professionals, and HVAC technicians to detect and measure AC leakage currents in electrical systems. Leakage current can occur when there are insulation faults, equipment malfunctions, or other electrical issues, and monitoring it is crucial for safety and troubleshooting.
The Amprobe AC50 A is specifically designed to measure low levels of AC leakage current, making it perfect for detecting issues that could be dangerous or lead to equipment malfunction. It can measure current leakage from as low as 0.001 mA up to 60A.
Amprobe AC50A Key Features
- AC current measurement to 60A
- Leakage current measurement with resolution of 0.01mA
- AC voltage to 400V
- Resistance measurement and continuity beeper
- Min/Max control to see largest or smallest values in a series of measurements
- Relative value measurement to determine differentials
- Data Hold to freeze measurement value on the display
- Digital display with Analog bargraph
- Jaw opening 30 mm (1.2 in)
- Auto-Power-Off to save battery life
- Minimum Resolution 0.01mA
Specifications
| Feature | Specification |
| Display | 3-3/4, LCD incl. functions and symbols |
| Bargraph | 40 segments |
| Range Selection | Manual |
| Auto-Power-Off | Approx. 30 min. |
| Overload Display | The left digit is blinking |
| Measuring Rate (Bargraph) | 20 measurements/sec. |
| Measuring Rate (LCD) | 2 measurements/sec. |
| Clamp Opening | Ca. 30 mm (1.2”) |
| Overvoltage Category | CAT II, 600 V, CAT III, 300 V |
| Pollution Degree | 2 |
| Height Above MSL | Up to 2000 m, indoor operation |
| Battery Display | At low battery |
| Power Supply | Battery 2 x 1.5 V IEC LR6 (alkaline) |
| Current Consumption | Approx. 10 mA |
| Operation Temperature | -10° C … 50° C (14° F… 122° F) |
| Storage Temperature | -20° C … 60° C (-4° F… 140° F) |
| Humidity | < 75 % relative humidity |
| Dimension | 183 x 63.6 x 35.6 mm (7.2 x 2.5 x 1.4 inch) |
| Weight | Ca. 190 g (7 oz) |