Megger BM5200 5 kV Insulation Resistance Tester
Short Description:
Shop Megger BM5200 at competitive prices in Dubai, UAE. Upgrade your electrical testing tools effortlessly.
Product purchase
Call for Best Price In UAE 00971(04) 447 6031 00971(04) 344 9868
16
People watching this product now!
Terms of sending goods ›
- In-stock items are delivered within 2 business days.
- We are not Supporting COD Payments Terms Outside UAE
Megger BM5200 5 kV Insulation Resistance Tester
The Megger BM5200 5 kV insulation resistance tester is engineered for high voltage insulation resistance testing, ideal for maintaining and servicing cables, rotating machinery, transformers, switchgear, and various industrial applications. The BM5200 allows you to conduct DC insulation tests at voltages of 250 V, 500 V, 1000 V, 2500 V, and 5000 V. It has an insulation resistance measurement range from 100 kΩ to 1000 GΩ. Additionally, it offers an automatic discharge for capacitive circuits under test and shows the decaying voltage.
The instrument operates on battery power and features both a digital and analogue arc display. It includes a guard terminal to enhance accuracy by reducing the impact of surface leakage, which can cause measurement errors. for more insulation resistance meter visit our website.
Megger BM5200 Key Features
- 1 TΩ, 1.4 mA, 5 kV digital insulation tester with digital and analogue display
- Five test ranges; 250 V, 500 V, 1000 V, 2500 V and 5000 V
- Insulation (InS), Polarisation Index (PI) and variable timed test (t) modes
- Selectable DC or AC (incl. frequency) voltmeter functions
- Guard terminal to shunt surface leakage currents
- CAT III 600 V safety rating
Megger BM5200 Specifications
Feature | Specification |
---|---|
Insulation range | 100 kΩ to 1 TΩ |
Nominal test voltages | 250 V, 500 V, 1000 V, 2500 V, 5000 V |
Terminal voltage accuracy | <1000 V: 0…+10% of nominal test voltage |
≥1000 V: 0…+5% of nominal test voltage | |
Insulation accuracy | Up to 1 GΩ: All ranges ±5% ±2 digits |
Over 1 GΩ: | |
5000 V: ±5% ±0.04% per GΩ | |
2500 V: ±5% ±0.08% per GΩ | |
1000 V: ±5% ±0.2% per GΩ | |
500 V: ±5% ±0.4% per GΩ | |
250 V: ±5% ±0.8% per GΩ | |
Short circuit/charge current | 1.4 mA ±0.5 mA |
Maximum capacitance of load | 5 μF |
Voltmeter accuracy | 3% ± 3 V |
Frequency measurement | 45 Hz to 65 Hz |
Frequency measurement accuracy | ±2 Hz |
Voltmeter range | Up to 600 V a.c. or d.c. |
Power supply | 8 x LR6/AA batteries |
Battery life | 5 hours @ 5 kV into 100 MΩ with AA Alkaline LR6 |
Guard | 2% error guarding 5 MΩ leakage on 100 MΩ load |
Operating temperature range and humidity | -20 °C to +55 °C, 90% RH (0 °C to 40 °C), 70% RH (40 °C to 55 °C) |
Storage temperature range and humidity | -20 °C to +65 °C |
IP rating | IP40 |
Safety protection | Insulation Cat III 600 V |
Note | Service error with stated environmental limits is twice intrinsic error |
EMC | The product conforms to IEC 61326 |
Dimensions | 220 mm x 115 mm x 163 mm |
Weight | 1.45 kg |
Specifications
Feature | Specification |
---|---|
Insulation range | 100 kΩ to 1 TΩ |
Nominal test voltages | 250 V, 500 V, 1000 V, 2500 V, 5000 V |
Terminal voltage accuracy | <1000 V: 0…+10% of nominal test voltage |
≥1000 V: 0…+5% of nominal test voltage | |
Insulation accuracy | Up to 1 GΩ: All ranges ±5% ±2 digits |
Over 1 GΩ: | |
5000 V: ±5% ±0.04% per GΩ | |
2500 V: ±5% ±0.08% per GΩ | |
1000 V: ±5% ±0.2% per GΩ | |
500 V: ±5% ±0.4% per GΩ | |
250 V: ±5% ±0.8% per GΩ | |
Short circuit/charge current | 1.4 mA ±0.5 mA |
Maximum capacitance of load | 5 μF |
Voltmeter accuracy | 3% ± 3 V |
Frequency measurement | 45 Hz to 65 Hz |
Frequency measurement accuracy | ±2 Hz |
Voltmeter range | Up to 600 V a.c. or d.c. |
Power supply | 8 x LR6/AA batteries |
Battery life | 5 hours @ 5 kV into 100 MΩ with AA Alkaline LR6 |
Guard | 2% error guarding 5 MΩ leakage on 100 MΩ load |
Operating temperature range and humidity | -20 °C to +55 °C, 90% RH (0 °C to 40 °C), 70% RH (40 °C to 55 °C) |
Storage temperature range and humidity | -20 °C to +65 °C |
IP rating | IP40 |
Safety protection | Insulation Cat III 600 V |
Note | Service error with stated environmental limits is twice intrinsic error |
EMC | The product conforms to IEC 61326 |
Dimensions | 220 mm x 115 mm x 163 mm |
Weight | 1.45 kg |
Rated 0 out of 5
0 reviews
Rated 5 out of 5
0
Rated 4 out of 5
0
Rated 3 out of 5
0
Rated 2 out of 5
0
Rated 1 out of 5
0
Be the first to review “Megger BM5200 5 kV Insulation Resistance Tester” Cancel reply
You must be logged in to post a review.
Related Products
Kyoritsu KEW 3552BT Digital Insulation / Continuity Tester
Rated 0 out of 5
In stock
Kyoritsu KEW 3551 Digital Insulation / Continuity Tester
Rated 5.00 out of 5
In stock
Reviews
Clear filtersThere are no reviews yet.