Megger OCR50D Oil Circuit Recloser Test Set

Short Description:

Buy the Megger OCR50D at a competitive price! Ensure safety and efficiency in your electrical testing with this premium device.

Product purchase

SKU: 92543 Category:
Brand:Megger

Call for Best Price In UAE 00971(04) 447 6031 00971(04) 344 9868

15 People watching this product now!

Terms of sending goods ›

  •  In-stock items are delivered within 2 business days.
  • We are not Supporting COD Payments Terms Outside UAE

Megger OCR50D

The Megger OCR50D Automatic Oil Circuit Recloser Test Set is a self-contained, mobile unit specifically designed to verify the correct operation of automatic circuit reclosers under simulated overload and fault conditions. This testing is crucial for ensuring reliable system performance, protection, and coordination.

The OCR50D features a digital control and instrumentation system, providing straightforward operation and precise test results. It also offers a variable high-current output with an impedance compensation network to stabilize the output current during testing.

The Automatic Oil Circuit Recloser Test Sets are capable of testing reclosers with either oil or vacuum interrupters. Additionally, they can conduct primary injection (high-current) testing on electronically controlled reclosers. The following are common tests performed on reclosers using these test sets.

Megger OCR50D Key Features

  • Preprogrammed test sequences for reclosers
  • Impedance compensation to properly test reclosers with variable impedance characteristics
  • Accurate duplication of test results
  • Simple operation and precise test results
  • Full color, high resolution, TFT LCD touch screen
  • OCR software runs under PowerDB software suite
  • View, save and export test reports for printing or importing into PowerDB
  • Digitized TCC Curves included in the OCR software
  • Simplified Control Software – easy to learn and use

Datasheet

Mme-Pdfs-Image

specifications

Megger OCR50D Specifications

Input Specifications
Model No. Input Voltage (Single-Phase) Input Frequency
OCR15D-208/60 208 V ±5% at 150 A, 230 V ±5% at 150 A, 460 V ±5% at 40 A, 575 V ±5% at 35 A 50/60 Hz
OCR15D-220/50 220 V ±5% at 150 A, 240 V ±5% at 150 A, 380 V ±5% at 40 A, 415 V ±5% at 35 A 50/60 Hz
OCR50D-460 460 V ±5% at 150 A 50/60 Hz
OCR50D-400 400 V ±5% at 150 A 50/60 Hz
Output Specifications
Model Output Rating Rated Output Ranges
OCR15D 15 kVA 0 to 2000 A at 7.5 V max, 0 to 1500 A at 10 V max, 0 to 1000 A at 15 V max, 0 to 500 A at 30 V max, 0 to 250 A at 60 V max, 0 to 100 A at 150 V max, 0 to 50 A at 300 V max, 0 to 25 A at 600 V max
OCR50D 50 kVA 0 to 2800 A at 18 V max, 0 to 2000 A at 25 V max, 0 to 1400 A at 36 V max, 0 to 1000 A at 50 V max, 0 to 700 A at 71.5 V max, 0 to 500 A at 100 V max, 0 to 350 A at 143 V max, 0 to 250 A at 200 V max, 0 to 150 A at 334 V max, 0 to 100 A at 500 V max, 0 to 50 A at 1000 V max