The GW Instek GPM 8213 is a important apparatus for engineers, professionals, and analysts working with single-phase AC control supplies. It gives them with the vital estimations and investigation capabilities to assess the execution, productivity, and quality of their control supply frameworks. Whether it’s for vitality reviews, control utilization examination, or control quality checking, the GPM-8213 offers a dependable and precise arrangement for single-phase control estimations.

  • Safe Buy
  • Fast Delivery
  • Original Guarantee
  • Online Payment

Manual

Manual

Manual

specifications

Item Spec.
Input voltage 600 Vrms
Input current 20 Arms
Input impedance (50/60 Hz) — Voltage 2.4 MΩ
Input impedance (50/60 Hz) — Current 5 mA – 200 mA: 500 mΩ
0.5 A – 20 A: 5 mΩ
Maximum display voltage 700 Vrms
Maximum display current 25 Arms
Maximum allowable isolation voltage 300 V
Low frequency filter Cut-off frequency 500 Hz
Display / Processing
Synchronization frequency 45 Hz ∼ 6 kHz
Refresh rate 10 times/sec
Average 1, 2, 4, 8, 16, 32, 64
Displayed mode Standard: 8 items simultaneously.
Simple: 4 items simultaneously.
Displayed digits 5
Voltage converter (PT ratio) 1 to 9,999.999
Current converter (CT ratio) 1 to 9,999.999
Measurement items
Voltage Vdc, Vrms, V+pk, V-pk
Current Idc, Irms, I+pk, I-pk
Power P, P+pk, P-pk, VA, VAR
Factors Crest Factor: CFV, CFI   |   Power Factor: PF
Frequency VHz, IHz
Angle DEG
Total Harmonic Distortion THDV, THDI
Integration Time, WP, WP+, WP-, q, q+
Voltage Measurement
Measurement range CF = 3: 15 V, 30 V, 60 V, 150 V, 300 V, 600 V
CF = 6: 7.5 V, 15 V, 30 V, 75 V, 150 V, 300 V
Crest factor 3, 6
Accuracy Effective range: 1% to 105% of range
DC: ±(0.2% reading + 0.2% range)
45 Hz ≤ f ≤ 66 Hz: ±(0.1% reading + 0.1% range)
66 Hz < f ≤ 1 kHz: ±(0.1% reading + 0.2% range)
1 kHz < f ≤ 6 kHz: ±3% of range
Filter ON: Increase 0.3% reading @ 45–66 Hz
Temperature effect 5–18 °C / 28–40 °C: Increase ±0.03% reading / °C
Residual noise 0.5% of range
Current Measurement
Measurement range CF = 3: 5 mA, 10 mA, 20 mA, 50 mA, 100 mA, 200 mA, 500 mA, 1 A, 2 A, 5 A, 10 A, 20 A
CF = 6: 2.5 mA, 5 mA, 10 mA, 25 mA, 50 mA, 100 mA, 250 mA, 0.5 A, 1 A, 2.5 A, 5 A, 10 A
Crest factor 3, 6
Accuracy Effective range: 1% to 105% of range
DC: ±(0.2% reading + 0.2% range)
45 Hz ≤ f ≤ 66 Hz: ±(0.1% reading + 0.1% range)
66 Hz < f ≤ 1 kHz: ±(0.1% reading + 0.2% range)
1 kHz < f ≤ 6 kHz: ±3% of range
Filter ON: Increase 0.3% reading @ 45–66 Hz
Temperature effect 5–18 °C / 28–40 °C: Increase ±0.03% reading / °C
Residual noise 0.5% of range
Power Measurement
Accuracy Effective range: 1% to 110% of range
DC: ±(0.2% reading + 0.2% range)
45 Hz ≤ f ≤ 66 Hz: ±(0.1% reading + 0.1% range)
66 Hz < f ≤ 1 kHz: ±(0.1% reading + 0.3% range)
1 kHz < f ≤ 6 kHz: ±3% of range
Filter ON: Increase 0.3% reading @ 45–66 Hz
Temperature effect (5–18 °C / 28–40 °C): Increase ±0.03% reading / °C
Frequency Measurement
Measurement range Filter ON: 30.000 Hz to 499.99 Hz
Filter OFF: 30.000 Hz to 9.9999 kHz
Measurement items Voltage, Current
Effective input range 10% to 105% of voltage input range
Accuracy ±0.06% reading
Integrator Measurement
Integrator accuracy ±(Accuracy of voltage or current + 0.1% reading)
Time range 0 h 0 min to 9999 h 59 min
Time accuracy ±0.01% ±1 s
General
Display 4″ TFT LCD
Interfaces Standard: RS-232C, USB device, LAN   |   Optional: GPIB
Power source AC 100–240 V, 50–60 Hz
Power consumption 25 VA max.
Dimensions & weight 270 (W) × 110 (H) × 350 (D) mm, Approx. 2.9 kg