Megger TORKEL 910 Battery Load Unit

Brand: Megger
SKU: 125487
Share

The Megger TORKEL 910 is a portable battery load unit for discharge and capacity testing of stationary battery banks in service, delivering up to 110 A at system voltages to 300 V with constant-current, constant-power, constant-resistance and profile discharge modes.

  • Safe Buy
  • Fast Delivery
  • Original Guarantee
  • Online Payment

Specifications

Specifications – Megger TORKEL 900-Series

Specifications are valid at nominal input voltage and an ambient temperature of +25°C (77°F). Specifications are subject to change without notice.

Environment
Application field Intended for use in high-voltage substations and industrial environments
Operating temperature 0°C to +50°C (32°F to +122°F), power derating above +35°C (+95°F)
Storage & transport -40°C to +70°C (-40°F to +158°F)
Humidity 5% – 95% RH, non-condensing
Shock / Vibration / Fall Instrument only: ETSI EN 300 019-2-7 class 7M2
Instrument in transport case: ISTA 2A
Altitude Operating: 3000 m (10000 ft)
Storage: 10000 m (33000 ft)
Encapsulation class IP20
CE-marking LVD 2014/35/EU, EMC 2014/30/EU, RoHS 2011/65/EU
General
Mains voltage 100 – 240 V AC, 50/60 Hz
Power consumption 200 W (max)
Power interruption 40 ms (max)
Protection Thermal cut-outs, automatic overload protection, emergency stop button
Dimensions 519 × 315 × 375 mm (20.5 × 12.4 × 14.7 in)
Weight Instrument: 19.5 kg (43 lbs)
With standard transport case: 31.9 kg (70.3 lbs)
With large transport case and cables: 39.2 kg (86.4 lbs)
Display 7″ LCD, capacitive touch screen
Available languages Czech, English, French, German, Romanian, Russian, Spanish, Swedish
Number of test files 30 (max)
Test time 240 h (max)
Measurement Section
Current measurement (display range) 0.0 to 2999.0 A
Current measurement inaccuracy ±(0.5% of reading + 0.1 A)
Resolution 0.1 A
Internal current measurement range TORKEL 910: 0 to 110 A
TORKEL 930/950: 0 to 220 A
Input for clamp-on probe Range: 0 to 1000 mV DC
mV/A ratio: 0.30 to 100.00 mV/A
Input impedance: >1 MΩ
Voltage measurement 0 to 500 V DC
Inaccuracy: ±(0.5% of reading + 0.1 V DC)
Resolution: 0.1 V
Sample rate: 10 Hz, values saved when change >10 mV
Time measurement Inaccuracy: ±0.1% of reading ±1 digit
Load Section
Battery voltage 7.5 V¹ to 300 V¹ / 500 V²
Power 15 kW (max)
Load patterns Constant current, constant power, constant resistance, current or power profile
Constant I range TORKEL 910: 0 to 110.0 A
TORKEL 930/950: 0 to 220.0 A
Inaccuracy: ±(0.5% +0.2 A)
Resolution: 0.1 A
Ripple max: 0.5 A peak
Constant R range 300 mΩ to 3 kΩ, Inaccuracy ±1% typical, Resolution 100 mΩ
Constant P range 0 to 15 kW, Inaccuracy ±1% typical, Resolution 10 W
Inputs +7.5 to 300 V¹ / 7.5 to 500 V², –0 V, I EXT ≤ 1 V DC, Voltage sense impedance >1 MΩ
Outputs ALARM relay: 28 V DC, 8 A / 240 V AC, 8 A
TXL STOP relay: 250 V DC 0.28 A, 28 V DC 8 A, 250 V AC 8 A
9 V DC ±7% max 100 mA
Communication ports BVM1/BVM2 USB for BVM units, USB for memory, PC connection for reports

 

0 reviews
0
0
0
0
0

There are no reviews yet.

Be the first to review “Megger TORKEL 910 Battery Load Unit”