Megger MIT481-2 Insulation And Continuity Tester

(1 customer review)

Short Description:

Buy the Megger MIT481-2 at unbeatable prices! Discover its features and elevate your testing capabilities today. Limited stock available!

Product purchase

SKU: 5041 Category:
Brand:Megger

Call for Best Price In UAE 00971(04) 447 6031 00971(04) 344 9868

15 People watching this product now!

Terms of sending goods ›

  •  In-stock items are delivered within 2 business days.
  • We are not Supporting COD Payments Terms Outside UAE

Megger MIT481-2

The Megger MIT481-2 is a robust and versatile insulation tester designed for electrical professionals who need reliable performance in various environments. It is part of the MIT400 series, which is well-regarded for its advanced features and durability. The MIT481-2 offers several key functionalities that make it suitable for a wide range of applications, including telecommunications, data communications, and general electrical testing.

The three-terminal measurement design allows the connection of all three test leads—A, B, and E (or Tip, Ring, and Ground). The measurement pair can be selected directly using the A-B-E (T-R-G) button on the front panel, with the selection confirmed on the display. This setup eliminates the need to disconnect test leads when measuring individual pairs.

The Megger MIT481-2 and MIT485-2 Insulation and Continuity Testers are specifically designed to meet the rigorous demands of communications engineers who require reliable, accurate, and versatile tools for testing and maintaining telecommunications equipment and installations. Both models are part of Megger’s renowned range of electrical test equipment, known for their durability and precision in the field.

Key Features of the Megger MIT481-2 and MIT485-2

  • Insulation testing up to 500 V and 100 GΩ range in a hand held instrument
  • 3 wire connection for A, B and E (Tip, Ring and Earth) connection (New)
  • Gated access to 500 V to prevent accidental damage (New)
  • Rechargeable options for mains and car charging (New)
  • Single range, faster continuity testing from 0.01 Ω to 1 MΩ (New)
  • Differential measurement capability (New)
  • Stabilized insulation test voltage (New)
  • 600 V Trms AC and DC voltage measurement
  • Test result storage and Bluetooth® downloading
  • CAT IV 600 V and IP 54

specifications

Parameter Specification
Insulation Test Voltage (Nominal) 50 V, 100 V, 250 V, 500 V
Insulation Accuracy 50 V: 10 GΩ ± 2% ± 2 digits ± 4.0% per GΩ
100 V: 20 GΩ ± 2% ± 2 digits ± 2.0% per GΩ
250 V: 50 GΩ ± 2% ± 2 digits ± 0.8% per GΩ
500 V: 100 GΩ ± 2% ± 2 digits ± 0.4% per GΩ
Service Error 50V: ± 2.0% ± 2d, 100kΩ – 900kΩ ± 10.5%
100V: ± 2.0% ± 2d, 100kΩ – 900kΩ ± 10.3%
250V: ± 2.0% ± 2d, 100kΩ – 900kΩ ± 10.3%
500V: ± 2.0% ± 2d, 100kΩ – 900kΩ ± 10.3%
Display Range (Analogue) 1 GΩ full scale
Resolution 0.1 kΩ
Short Circuit/Charge Current 2 mA +0% -50% to EN 61557-2 (2007)
Open Circuit Voltage Insulation -0% +2% ± 2 V
Test Current 1 mA at min. pass value of insulation to a maximum of 2 mA max.
EN61557 Operating Range 0.10 MΩ to 1.0 GΩ
Leakage Current 10% ±3 digits
Timer Control Countdown timer 60 second
Continuity Range 0.01 Ω to 1.0 MΩ
Continuity Accuracy ± 3% ± 2 digits (0 to 100 Ω)
±5% ±2 digits (>100 Ω- 500 kΩ)
(>500 kΩ – 1 MΩ unspecified)
Service Error (Continuity) ± 2.0%, 0.1Ω – 2Ω ± 6.8%
Open Circuit Voltage (Continuity) 5 V ± 1 V
Test Current (Continuity) 200 mA (–0 mA +20 mA) (0.01 Ω to 4 Ω)
Lead Resistance Nulling Nulling up to 10 Ω
mA Range (DC) 0.0mA – 500mA: +/-5%, +/-2 digits
mA Range (AC) 0.0mA – 10.0mA: unspecified
10.0mA – 500mA: +/-5%, +/-2 digits (15Hz – 400Hz, sinusoidal)
Voltage Range (AC) 10 mV to 600 V TRMS sinusoidal (15 Hz to 400 Hz)
Voltage Range (DC) 10 mV to 600 V
Volt Range Accuracy (AC) ± 2% ± 2 digits
Volt Range Accuracy (DC) ± 2% ± 2 digits
Service Error (Voltage) ± 2.0% ± 2d, 0V – 300Vac/dc ± 5.1%
Waveform Accuracy Non-sinusoidal waveforms: ±3% ± 2 digits >100 mV to 600 V TRMS
±8% ± 2 digits 10 mV to 100 mV TRMS
Default Voltmeter Operation Operates at > 25 volts ac or dc on any range except OFF
Frequency Measurement Range 15 Hz – 400 Hz
Frequency Measurement Accuracy ±0.5% ± 1 digit
Capacitance Range 0.1 nF to 10 μF
Capacitance Accuracy ± 5.0% ± 2 digits (1 nF-10 μF)
Cable Coefficient 40nF/km to 70nF/km
Unit of measure: 50nF/km
Result Storage Capacity >1000 test results
Data Download Bluetooth® wireless, Class II, Range up to 10 m
Power Supply 6 x 1.5 V cells, IEC LR6 (AA, MN1500, HP7, AM3 R6HP) Alkaline
6 x 1.2 V NiMH rechargeable cells may be used
Battery Life 3000 insulation tests with duty cycle of 5 sec ON /55 sec OFF @ 500 V into 500 kΩ
Charger (Optional) 12-15 V dc (accessory interface)
Dimensions 228 mm x 108 mm x 63 mm (9.00 in x 4.25 in x 2.32 in)
Weight 800 g (1.8 lb)
Weight (Instrument and Case) 1.75 kg (3.86 lb)

Datasheet

Mme-Pdfs-Image

5
1 review
1
0
0
0
0

1 review for Megger MIT481-2 Insulation And Continuity Tester

Clear filters
  1. Carol

    It has a 3-wire connection