MEGGER MFM10 Sheath Fault Location System

The MEGGER MFM10 SHEATH FAULT LOCATION SYSTEM intuitive, menu supported operator guidance of the MFM 10 works using the well accepted SebaKMT Easy-Go principle.

(1 customer review)
SKU: 4195

Call for Price

We are not Supporting COD Payments Terms Outside UAE

16 People watching this product now!

MEGGER MFM10 Sheath Fault Location System

The MEGGER MFM10 Sheath Fault Location System is a sophisticated and efficient tool designed for the testing, pre-location, and pinpointing of sheath faults in cables. Renowned for its ease of use, precision, and speed, the MFM10 employs the menu-supported ‘Easy Go’ test system. This intuitive interface simplifies operation, allowing users to quickly interpret results with minimal training. Consequently, the MFM10 enables automatic testing of cables, accurate evaluation of measured data, and provides a fast, reliable means to assess cable sheath insulation and identify faults.

One of the standout features of the MFM10 is its bipolar pre-location capability. This advanced feature enhances the detection of galvanic and thermoelectric influences, thereby improving the accuracy and quality of pre-location efforts. The system also supports a multi-section facility, allowing for the entry of cable segments with varying parameters, which is particularly useful for managing complex cable networks.

For difficult cable faults, the MFM10 offers a high current output of up to 750 mA, which can effectively ‘burn’ through challenging faults to facilitate accurate pinpointing. Moreover, the integrated protocolling feature, in conjunction with the approved MeggerBook RE software, allows for the seamless generation of comprehensive test reports. This functionality ensures that all test data is meticulously documented and easily accessible for review and analysis.

MEGGER MFM10 SHEATH FAULT LOCATION SYSTEM Specifications:

  • Functions: Testing, prelocation and pinpointing, burning, direct resistance measurement, voltage and current limiter, quick event/transient recognition
  • Display:5.7’’ 320 x 240; LCD, LED backlight
  • User Interface:Rotary encoder & touch screen
  • Output voltage0 :… 10 kV DC, bipolar
  • Output current:750 mA @ 0,4 kV, 200 mA @ 0,4 … 1,5 kV 60 mA @ 5 kV, 30 mA @ 10 kV
  • Pinpointing:0 … 10 kV DC pulsed
  • Pulse rates:0,5:1; 1:2; 1,5:0,5; 1,5:3,5 4.8 Hz for the use with A-Frame
  • Accuracy: ± 0,1% for the fault location relative to the cable length
  • Audio frequency (option) :8,44 kHz, 15 W
  • Protocolling:MeggerBook RE Software via USB stick
  • Mains Supply:88 … 264 V, 50 … 60 Hz, 800 VA
  • Battery:NIMH, 340 Wh, for all operations
  • DC supply:12 V … 24 V DC / charge only
  • Max. discharge capacity:10 μF
  • Operation conditions:- 25 °C … + 55 °C, 93 % rel. humidity
  • Dimensionsl500 x 457 x 305 mm
  • Weight:25 kg including cable
  • Protection class:IP 53, with lid closed
5
1 review
1
0
0
0
0

1 review for MEGGER MFM10 Sheath Fault Location System

Clear filters
  1. Ilyas

    Thank you

    0
    0
Add a review

Brand

Megger

Megger

Megger since 1889 is a leading global premium manufacturer of measurement and testing technology. Megger top priority has always been to make your everyday work easier and safer. As such, insulation testers, micro-ohmmeters, and multimeters are among the long line of Megger inventions, making this brand one of the pioneers in the electrical industry. Megger products combine many years of experience and the valued feedback from our global users with the inventiveness and conscientiousness of our product developers. In Germany, we manufacture at three sites, Aachen, and Baunach near Bamberg and Radeburg near Dresden. Other manufacturing locations are based in Sweden, England, and America.

Megger logo brand

DATA sheet

Data Sheet

Specifications






MFM10 Technical Specifications


MFM10 Technical Specifications

Specification Details
Functions Testing, prelocation and pinpointing, burning, direct resistance measurement, voltage and current limiter, quick event/transient recognition
Display 5.7’’ 320 x 240; LCD, LED backlight
User Interface Rotary encoder & touch screen
Output voltage 0 … 10 kV DC, bipolar
Output current 750 mA @ 0,4 kV, 200 mA @ 0,4 … 1,5 kV, 60 mA @ 5 kV, 30 mA @ 10 kV
Pinpointing 0 … 10 kV DC pulsed
Pulse rates 0,5:1; 1:2; 1,5:0,5; 1,5:3,5, 4.8 Hz for the use with A-Frame
Accuracy ± 0,1% for the fault location relative to the cable length
Audio frequency (option) 8,44 kHz, 15 W
Protocolling MeggerBook RE Software via USB stick
Mains Supply 88 … 264 V, 50 … 60 Hz, 800 VA
Battery NIMH, 340 Wh, for all operations
DC supply 12 V … 24 V DC / charge only
Max. discharge capacity 10 μF
Operation conditions – 25 °C … + 55 °C, 93 % rel. humidity
Dimensions 500 x 457 x 305 mm
Weight 25 kg including cable
Protection class IP 53, with lid closed