Fluke 1663 Multifunction Testers

(1 customer review)

Short Description:

The Fluke 1663 Multifunction Testers installation tester delivers the full-featured functionality and advanced measurement capabilities that professional installers need.

Product purchase

SKU: 3105 Category:
Brand:Fluke

Original price was: AED 7,700.Current price is: AED 7,500. (excl.VAT)

2 in stock

17 People watching this product now!

Terms of sending goods ›

  •  In-stock items are delivered within 2 business days.
  • We are not Supporting COD Payments Terms Outside UAE

Fluke 1663 Multifunction Testers

The Fluke 1663 installation tester delivers the full-featured functionality and advanced measurement capabilities that professional installers need. It is compact and lightweight (less than 1.3 kg) and has a padded carrying and waist strap for convenient handling.

Operation is intuitive and easily mastered by all levels of workers so you can put it to work immediately for quick and efficient testing to all local regulations. Additional helpful features like On/Off switchable auto-start for RCD and loop test, and self-test save time and give you more confidence in your results.

Fluke 1663 Multifunction Testers specifications:

  • AC voltage measurement:
  • Range:500 V
  • Resolution:0.1 V
  • Accuracy 45 Hz – 66 Hz:0.8% + 3
  • Input impedance:360 kΩ
  • Overload protection:660 V rms
  • Test current:1 mA @ 50 kΩ
    1 mA @ 100 kΩ
    1 mA @ 250 kΩ
    1 mA @ 500 kΩ
    1 mA @ 1 MΩ
  • Resolution:0.01 MΩ / 0.1 MΩ
    0.01 MΩ / 0.1 MΩ
    0.01 MΩ / 0.1 MΩ
    0.01 MΩ / 0.1 MΩ / 1 MΩ
    0.01 MΩ / 0.1 MΩ / 1 MΩ
  • Insulation resistance range:20 MΩ /50 MΩ
    20 MΩ / 100 MΩ
    20 MΩ / 200 MΩ
    20 MΩ / 200 MΩ / 500 MΩ
    20 MΩ / 200 MΩ / 1000 MΩ
  • Computation:Prospective earth fault current (PEFC) or Prospective short circuit current (PSC) determined by dividing measured mains voltage by measured loop (L-PE) resistance or line (L-N) resistance, respectively.
  • RCD/FI-Tripping Current Measurement/Ramp Test (IΔN):
  • Current range:30% to 110% of RCD rated current
  • Step size:10% of IΔN
  • Measurement accuracy:±5%
  • Specified trip current ranges (EN 61008-1):50% to 100% for Type AC
    35% to 140% for Type A (>10 mA)
    35% to 200% for Type A (≤10 mA)
    50% to 200% for Type B
    ²5% for Type B

DataSheet

Data Sheet

5
1 review
1
0
0
0
0

1 review for Fluke 1663 Multifunction Testers

Clear filters
  1. Carol

    its good

Add a review